Jøtul GF 300 DV II Allagash Installation And Operation Instructions Manual page 11

Direct vent gas stove
Table of Contents

Advertisement

Vent Windows for Propane
35 Ft.
(10.67 m)
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
A
20 Ft.
C
(6.10 m)
15 Ft.
(4.57 m)
12 Ft.
(3.65 m)
C
Min. Vertical
8 Ft.
Termination
(2.43 m)
5 Ft.
(1.52 m)
Min. Rise
2 Ft.
(.60 m)
5 Ft.
(1.52 m)
F400 Coaxial Vent Window - LP
• VENTING MUST TERMINATE (END) WITHIN ONE OF THE
DESIGNATED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT CORRE-
SPONDS TO THE VENT TERMINATION AREA IN THE DIAGRAM ABOVE.
When termination is exactly on a division line, use the less restric-
tive position. For example, if termination is at 10 ft./5ft., restriction
will be set at Position D.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the stove restrictor plate to the cor-
responding position as shown in Figure 7, page 9.
Figure 11. Coaxial Vent Termination Window / LP
COAXIAL VENT
Up to four 45° or
two 90° elbows
permitted in
addition to the
starter elbow.
D
10 Ft.
15 Ft.
20 Ft.
(3.05 m)
(4.57 m)
(6.09 m)
H O R I Z O N TA L R U N
COLINEAR VENT
(10.67 m)
Minimum
Vertical
Termination
(2.43 m)
45°
Elbow
Up
27 Ft.
(8.22m)
F400 Colinear Vent Window - LP
• VENTING MUST TERMINATE
(END) WITHIN THE SHADED
AREA.
• Adjust the Exhaust Restric-
tor to position C for a verti-
cal colinear termination.
• Max. Offset: 2 ft. (610 mm)
Figure 12 . Colinear Termination / LP
137775_Rev_K 7.29.10
35 Ft.
25 Ft.
(7.62 m)
C
8 Ft.
2 Ft.
(16 cm)
HORIZONTAL RUN
11