Jøtul GF 300 DV II Allagash Installation And Operation Instructions Manual page 10

Direct vent gas stove
Table of Contents

Advertisement

137775_Rev_K 7.29.10
Vent Windows for Natural Gas
35 Ft.
(10.67 m)
30 Ft.
(9.14 m)
25 Ft.
(7.62 m)
A
20 Ft.
(6.10 m)
15 Ft.
(4.57 m)
12 Ft.
(3.65 m)
B
Min. Vertical
8 Ft.
Termination
(2.43 m)
5 Ft.
(1.52 m)
Min. Rise
2 Ft.
(.60 m)
(1.52 m)
F400 Coaxial Vent Window - NG
• ALL VENTING MUST TERMINATE (END) WITHIN ONE OF THE
SHADED AREAS.
• SET STOVE EXHAUST RESTRICTOR TO THE POSITION THAT
CORRESPONDS TO THE VENT TERMINATION AREA IN THE DIA-
GRAM ABOVE. When termination is exactly on a division line,
use the less restrictive position. For example, if termination is
at 20 ft./10ft., restriction will be set at Position B.
• ALWAYS MAINTAIN THE PROPER CLEARANCES TO
COMBUSTIBLES.
The circled letter designations in the vent diagram correspond
to the Exhaust Restrictor Setting on the stove. First, determine
which vent termination zone is appropriate for your installation
and fuel type, then adjust the restrictor to the corresponding
position as shown in figure 7, page 9.
Figure 9. Coaxial Vent Termination Window / NG
10
COAXIAL VENT
Up to four 45° or
two 90° elbows
addition to the
starter elbow.
A
B
C
5 Ft.
10 Ft.
15 Ft.
(3.05 m)
(4.57 m)
H O R I Z O N TA L R U N
permitted in
D
20 Ft.
27 Ft.
(6.09 m)
(8.22m)
COLINEAR VENT
35 Ft.
35 Ft.
(10.67 m)
(10.67 m)
25 Ft.
25 Ft.
(7.62 m)
(7.62 m)
B
Minimum
Minimum
Vertical
Vertical
Termination
Termination
8 Ft.
8 Ft.
(2.43 m)
(2.43 m)
45°
Elbow
Up
2 Ft.
2 Ft.
(16 cm)
(16 cm)
HORIZONTAL RUN
• VENTING MUST TERMI-
NATE (END) WITHIN THE
SHADED AREA.
• Adjust the Exhaust Re-
strictor to position B for
any NG colinear termi-
nation.
• Max. Offset: 2 ft. (610
mm)
Figure 10 . Colinear Termination / NG