The controllers are programmed by dipswitches and trimmers in the MAN
mode, or by setting the internal parameters - in MEM mode, accessible
via programming key or via serial line.
4.1 Manual and standard internal
parameter programming
The functions that can be set manually using the dipswitches and
trimmers (Fig. 4.aa) are shown in the tables below, complete with the
Modbus variables used to read the manual settings.
ADDRESS
Mode dipswitches (S2)
Function
Dip S2.1
Select type of controller setting
Dip S2.2
Select type of analogue inputs
Dip S2.3
Select voltage/current input
If dipswitch S2.1 is ON, the standard internal parameters are used,
equivalent to those that can be set on the panel. These have the same
name, however with the suffi x MEM rather than FCR.
Function
Select operating frequency
Select operating curve
Select null input mode
Select baud rate for serial operation
MINIMUM setting (MIN)
MAXIMUM setting (MAX)
DELAY setting (DELAY)
Input control (IN)
The address parameter can be automatically selected, based on the
dipswitch settings. For details, see Table 4.a.d
Function
Select FCR address (ADDRESS)
DI = Discrete inputs
R digital variables
CO= Coils
R/W digital variables
IR = Input Register
R integer variables
HO= Holding Register
R/W integer variables
The digital variables are interpreted as 0=OFF , 1 = ON
"FCR3 three-phase controller" +030222150 - rel. 1.3 - 12.01.2021

4. PROGRAMMING THE CONTROLLER

ON
DIP
MEM
ON
1 2 3 4 5 6 7 8
S1
1
2 3 4 5 6 7 8
S2
MAN
FCR Manual
HZFCR
Dip S2.4
DI.2
LINFCR
Dip S2.5
DI.3
MICUTFCR
Dip S2.6
DI.4
BAUD1FCR
Dip S2.7
DI.5
BAUD2FCR
Dip S2.8
DI.6
MINFCR
TR1
IR.4
MAXFCR
TR2
IR.3
DELAYFCR
TR3
IR.2
INFCR
B-GND
IR.6
Manual
Memory
SADRFCR
SADRMEM
S1
IR.1
HO.2
BAUD
TR3
DIP
DIP
7 8
DELAY
Fig. 4.a
Modbus
State
Description
SEL
OFF:
MAN: set fundamental parameters from FCR panel
DI.1
ON:
MEM: set parameters in internal memory
OFF:
10V: 0/10 Vdc
ON:
PWM: 0/5 Vdc or PWM
OFF:
V: Voltage signal (selected via Dip2)
I: Current signal (Dip2 must be ON)
Internal Memory
State
HZMEM
OFF:
ON:
CO.2
LINMEM
OFF:
CO.3
ON:
OFF:
MICUTMEM
CO.4
ON:
BAUD1FCR
OFF:
BAUD2FCR
OFF:
9600
MINMEM
0-40
HO.4
MAXMEM
50-100 Maximum setting from 0-40% of the input voltage
HO.3
DELAYMEM
0-100
HO.2
INMEM
0-100
HO.7
State
Description
0-255 FCR
Device address
1-255 MEM
If SADRFCR=0 then the address in the memory is used
10
TR2
TR1
MAX
MIN
Description
50 Hz
60 Hz
LIN: linear curve
QUAD: quadratic curve
MIN: controller operates at minimum speed
COFF: control off (Cut-Off )
ON:
OFF:
BAUD
OFF:
ON:
19200
38400
Minimum setting from 0-40% of the input voltage
Response time to an input step. The range of adjustment
from 0-100% (clockwise) corresponds to setting the time
from 0-10 sec
Control signal at analogue input
Tab. 4.a
Tab. 4.b
Tab. 4.c