Installation And Wiring With A Powerware 9395 Ups - Eaton Powerware 9390 Installation And Operation Manual

Sync control
Hide thumbs Also See for Powerware 9390:
Table of Contents

Advertisement

3.2

Installation and Wiring with a Powerware 9395 UPS

EATON Powerware
NOTE When installing wiring connections, conduit must be installed between the Powerware Sync Control and
the UPS cabinet. Conduit also must be installed between the Powerware Sync Control and the customer's remote
monitoring system.
To install and wire:
1.
Install the Powerware Sync Control panel to the selected mounting location.
See Figure 2-1 on page 2−2 for mounting hole dimensions and Figure 2-2 on
page 2−3 for conduit entrance locations.
2.
Unfasten the front door latches and swing the door open.
3.
Complete all control wiring interconnections using Table 3-3 for wiring
requirements.
Figure 3-1 on page 3−3 shows the Powerware Sync Control TB1 terminal block
and ground terminal locations. Figure 3-2 on page 3−4 shows the TB1 terminal
block wiring detail.
Figure 3-6 through Figure 3-9 starting on page 3−9 show the typical locations of
the UPS TB3, TB6, and X−Slot
Figure 3-5 on page 3−6 shows the TB6 detail.
Refer to the applicable Powerware 9395 UPS Installation and Operation Manual
listed in paragraph 1.3 on page 1−4 for UPS cabinet terminal locations and
assignments, termination requirements, conduit landing locations, and terminal
access instructions.
NOTE Complete the wiring to the X−Slot Relay Interface Card terminals before installing the cards in the
Communication Bay in each of the UPS cabinets.
4.
Route wires through the strain relief bushing and connect to the terminals on the
X−Slot Relay Interface Card in each of the UPS cabinets (see Figure 3-10 on
page 3−13 and Figure 3-11 on page 3−13).
5.
Install the X−Slot Relay Interface Card into an open X−Slot communication bay on
the front of the UPS (see Figure 3-6 on page 3−9, Figure 3-7 on page 3−10,
Figure 3-8 on page 3−11, or Figure 3-9 on page 3−12). Refer to the applicable
Powerware 9395 UPS Installation and Operation Manual listed in paragraph 1.3
on page 1−4 for UPS cabinet access instructions.
6.
Verify the jumper is installed between Sync Control terminal TB1−40 and TB1−41
(see Figure 3-2 on page 3−4).
7.
If applicable, complete all customer remote monitoring system wiring
interconnections using Table 3-2 on page 3−3 for wiring requirements.
Figure 3-2 on page 3−4 shows the TB1 terminal block wiring detail.
8.
When all wiring is complete, close the door and secure the latch.
When connecting the bypass and load voltage from another model UPS to a Powerware 9395 UPS using the
Powerware Sync Control accessory, use Phase A, Phase B, and Neutral connections from the other UPS. DO NOT
connect the other model UPS Phase C bypass and load voltage to the Sync Control connection point when
connecting to a Powerware 9395 UPS.
®
9390 and 9395 Sync Control Installation and Operation Manual
POWERWARE SYNC CONTROL INSTALLATION
Relay Interface Card interconnect terminal blocks.
®
C A U T I O N
S
164201571 Rev E www.powerware.com
3−7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9395

Table of Contents