Mounting 110A- Or 110P-Type Terminal Blocks On The Wall - Avaya G650 Installing

Hide thumbs Also See for G650:
Table of Contents

Advertisement

Blue — To information outlets
White — From MDF to satellite locations (3-pair)
Each label identifies two rows on the terminal block. The upper half identifies the row above it
and the lower half identifies the row below it. The labels are inserted into the clear plastic
designation strips furnished with the terminal blocks. The strip is snapped in place between the
terminal block rows. Label code number 1220A (comcode 103970000) contains all of the
required labels.
Figure 49: Label graphic symbols and nomenclature
Figure notes:
1. Floor or Building Identification (write
as required
2. Media Gateway
3. Carrier (leave blank for G600 Media
Gateway)
4. Slot

Mounting 110A- or 110P-type terminal blocks on the wall

The 110A-type terminal blocks can be stacked in almost any arrangement at any height or
location on the wall.
arrangement. The distance between the mounting screw holes on the terminal blocks is 10.8
inches (27.4 centimeters). If a vertical patch cord trough is used, the distance between the
mounting screw holes is 5.31 inches (13.3 centimeters).
With 110P-type terminal blocks, the first block of the trunk/auxiliary field is aligned with the left
side of the media gateway. See
This arrangement allows for growth on the right side of the MDF.
To mount 110A- or 110P-type terminal blocks:
Figure 50: 110A-type terminal blocks (300-pair)
Figure 51: 110P-type terminal blocks (900-pair)
r758422i LJK 050996
5. Information Outlet
6. Site/Satellite Closet
7. Tie Circuit
8. Floor
9. Building
on page 123 shows one
Issue 2 January 2005
on page 124.
121