PVI 10kW / PVI 13kW / PVI 15kW
The ambient temperature must be between –25
The inverter will automatically reduce power or shut down to protect itself if ambient air
temperature rises above 50
The National Electrical Code (NEC) and Canadian Electrical Code require that the inverter be
connected to a dedicated circuit and no other outlets or device may be connected to this circuit. See
NEC Section 690-64(b)(1). The NEC also imposes limitations on the size of the inverter and the
manner in with it is connected to the utility grid. See NEC Section 690-64(b)(2).
The cooling air exhausts at the bottom of the unit. Nothing should block the 2" clear space under the
enclosure defined by the 2" tall mounting feet.
A minimum distance of 10" must be clear above the inverter for ventilation.
The inverter must be mounted with at least a 2" open space behind it. If wall-mounted, vertical, 2" x
2" uni-strut or channel can be used. Air should be able to flow behind the unit from below it to
above it.
If you are installing the inverter in a utility vault or electrical closet, the air circulation must be
sufficient for heat dissipation – provide external ventilation if necessary to maintain an ambient
condition of less than +50
Correct mounting positions for the inverter are shown on the following pages:
DOCR-060002 rev30
o
C.
o
C. The ambient temperature should be kept as low as possible.
Installation and Operation Manual
o
o
C and +50
C for full power, continuous operation.
8
July 7, 2010