Solectria Renewables PVI 10kW Installation And Operation Manual page 31

208, 240 and 480vac commercial, grid-tied photovoltaic inverter
Table of Contents

Advertisement

PVI 10kW / PVI 13kW / PVI 15kW
Input DC (PV) specifications for PVI 10KW / PVI 13KW / PVI 15KW inverter
Inverter Model
Operating Voltage Range (Power)
Input voltage MPP range
CEC full power range
Maximum open circuit voltage
(under all conditions)
Maximum input current
Maximum input power
(inverter limited)
Maximum recommended
PV power (modules @ STC)
(for 0-5 deg flat roof)
DC disconnect for PV positive (+)
Ground fault protection
Ground fault detection, must detect
Ground fault interrupt
Output to AC grid connection:
The PVI 10KW / PVI 13KW / PVI 15KW is designed to feed power into a standard 60Hz, 3-phase AC
utility service or AC provided within a facility by a step down transformer of not less than 15kVA. As
required by local codes, there must be a dedicated 3-phase circuit breaker for the PV inverter
connection.
208 VAC
240 VAC
480 VAC
208 VAC
240 VAC
480 VAC
DOCR-060002 rev30
PVI 10KW
205-430
205-385
235-380
475
52
10.6
12
13
included
0.75
0.75
PVI 10KW
40 A
40 A
40 A
PVI 10KW
183-228 V
212-264 V
423-528 V
Installation and Operation Manual
PVI 13KW
205-430
205-380
235-380
475
69
14
15-16
17
included
per UL 1741/2005 NEC 690.5
0.75
0.75
PVI 13KW
50 A
50 A
40 A
PVI 13KW
183-228 V
212-264 V
423-528 V
31
PVI 15KW
205-430
VDC
205-380
VDC
235-380
VDC
475
VDC
77
ADC
16
kW DC
16-18
kW DC
19
kW DC
included
0.75
A
0.75
A
PVI 15KW
60 A
60 A
40 A
PVI 15KW
183-228 V
212-264 V
423-528 V