Solectria Renewables PVI 50KW Installation And Operation Manual

Solectria Renewables PVI 50KW Installation And Operation Manual

Solectria inverter - installation and operation manual
Table of Contents

Advertisement

Quick Links

Installation and Operation Manual (Rev A) 
INSTALLATION AND OPERATION MANUAL 
 
 
 
 
 
 
DOCR‐070233
 
 
PVI 50KW 
PVI 60KW 
PVI 75KW 
PVI 85KW 
PVI 100KW 
 
 
© 2013, Solectria Renewables LLC 
PVI 50‐100KW Series Inverters 
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PVI 50KW and is the answer not in the manual?

Questions and answers

Summary of Contents for Solectria Renewables PVI 50KW

  • Page 1 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    PVI 50KW  PVI 60KW  PVI 75KW  PVI 85KW  PVI 100KW      INSTALLATION AND OPERATION MANUAL        © 2013, Solectria Renewables LLC          DOCR‐070233...
  • Page 2 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters                              IMPORTANT REGISTRATION AND  WARRANTY INFORMATION    For  warranty  to  become  active,  this  inverter  must  be  registered.  To  activate  warranty  and  register inverter, please visit the link below.    www.solectria.com/registration  DOCR‐070233  Page 2 of 92...
  • Page 3 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  IMPORTANT SAFETY INSTRUCTIONS  SAVE THESE INSTRUCTIONS    In this manual “inverter” or “inverters” refers to the inverter models: PVI 50KW, PVI 60KW, PVI  75KW, PVI 75KW‐PE, PVI 85KW, PVI 85KW‐PE, PVI 100KW and PVI 100KW‐PE unless one of the  specific models is noted.    This  manual  contains  important  instructions  that  shall  be  followed  during  installation  and  maintenance of the inverter.    To reduce the risk of electrical shock, and to ensure the safe installation and operation of the  inverter, the following safety symbols are used to indicate dangerous conditions and important  safety instructions:      WARNING: Use extreme caution when performing this task.  This indicates a fact or feature very important for the safety of the user  and/or which can cause serious hardware damage if not applied  appropriately.      NOTE: This indicates a feature that is important either for optimal and  efficient use or optimal system operation.      EXAMPLE: This indicates an example.   ...
  • Page 4 Tous les travaux d’installation électrique doivent être exécutés en conformité aux normes électriques locales  ainsi qu’à la norme nationale américaine et canadienne.     Le  PVI  ne  contient  aucune  pièce  requérant  un  entretient  effectué  par  l‘utilisateur.  Pour  toute  maintenance,  veuillez consulter Solectria Renewables ou un installateur agrée par Solectria Renewables (les coordonnées de  Solectria  Renewables  et  des  installateurs  agrées  sont  indiquées  sur  le  site  web  de  Solectria  Renewables:  www.solectria.com.     Avant d’installer ou d’utiliser le PVI veuillez lire toutes instructions et toutes les mises en garde présentes dans  ce manuel, sur le PVI et sur les modules PV. ...
  • Page 5: Table Of Contents

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Table of Contents  1 Introduction .......................... 7   2 Site Preparation and Inverter Placement .................. 9   2.1 Clearance Requirements  ..................... 10   2.2 Inverter Dimensions  ...................... 11   3 Installation .......................... 11   3.1 Checking For Shipping Damage  ................... 11   3.2 Inverter Lifting  ........................ 11   3.3 Mounting Details  ......................... 12   4 DC Connections from the PV Array and AC Connections to the Grid  ........ 14   4.1 Grounding ........................... 14   4.2 AC Grounding Connections  .................... 16   4.3 DC Grounding Connections ...
  • Page 6 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.11 Establishing Ethernet Connectivity ................... 49   6.12 Setting up TCP/IP Networking .................. 50   6.13 Viewing Current TCP/IP settings:  .................. 50   6.14 Manually Configuring Network Settings  ................ 52   6.15 Automatically Configuring Network Settings .............. 55   6.16 Setting Fallback IP Address .................... 56   6.17 Enabling SolrenView Web‐based Monitoring  .............. 59   6.18 Viewing and setting the Date/Time .................. 60   6.19 Rebooting the SolrenView Gateway  ................. 63   6.20 Resetting the SolrenView Gateway to Factory Defaults  ........... 64   6.21 Inverter Counts and Logs .................... 65   6.22 Displaying Error Counts  ..................... 66   6.23 Displaying Error Logs  ...................... 68  ...
  • Page 7: Introduction

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  1 Introduction  The PVI 50‐100KW inverter series are commercial, three‐phase grid‐tied PV inverters designed to  be  interconnected  to  the  electric  utility  grid.  By  following  this  manual  the  inverter  can  be  installed and operated safely. This installation guide is used as a reference for commissioning and  as a guideline on how to use the inverter most effectively.    Feeding  power  onto  the  grid  involves  conversion  of  the  DC  voltage  from  the  PV  array  to  grid  compatible AC voltage by inverting DC to AC. This unit feeds power into a standard, three‐phase ...
  • Page 8 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  AC Disconnect  LCD Display, Keypad,   & LED Indicators  DC disconnect  switch   Nameplate  Cooling Air Intake   Figure 1.2 – PVI Inverter (Front View)     Communications or  SolrenView AIR   Exhaust Air Output   Figure 1.3 – PVI Inverter (Rear View)    DOCR‐070233  Page 8 of 92...
  • Page 9: Site Preparation And Inverter Placement

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  2 Site Preparation and Inverter Placement  The inverter is comprised of a rainproof, industrial enclosure containing electrical and electronic  components and AC and DC integrated disconnecting means.    NOTE:  If  the  inverter  is  mounted  outside,  ensure  that  the  enclosure  and  disconnect  switch  doors  remain  closed  during  the  installation  process  in  case  of  rain  or  snow.   Leaving these doors open during installation will void the warranty.    NOTE: It is recommended to store the inverter indoors before installation. If the inverter  is  to  be  stored  outdoors  for  more  than  one  month  before  being  installed  and  commissioned, care must be taken to avoid condensation inside the unit. Removing the ...
  • Page 10: Clearance Requirements

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Inverter Model  Weight  PVI 50‐60KW  1,450 lbs  PVI 75‐85‐100KW  1,875 lbs  PVI 75‐85‐100KW‐PE  2,070 lbs  Table 2.1 – Weight of PVI 50‐100 Inverters     Installations in most US jurisdictions are subject to NFPA 70, known commonly by electricians  as  the  National  Electric  Code  (NEC).    The  NEC  requires  that  the  inverter  be  connected  to  a  dedicated circuit and no other outlets or devices may be connected to this circuit.  The NEC  also imposes limitations on the size of the inverter and the manner in which it is connected to  the utility grid.  See applicable revision of the NEC for more information. It is the installer’s  responsibility to follow all applicable electric codes.   2.1 Clearance Requirements   The  ambient  temperature  must  be  between  –40 F ...
  • Page 11: Inverter Dimensions

    Please  inspect  the  inverter  thoroughly  after  it  is  delivered.  If  any  damage  is  seen,  immediately  notify  the  shipping  company  to  make  a  claim.  If  there  is  any  question  about  potential  shipping  damage,  contact  Solectria  Renewables.  Photos  of  the  damage  will  be  helpful  in  documenting  potential shipping damage. ...
  • Page 12: Mounting Details

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters   Use  a  forklift  or  fork  attachment  or  other  equipment  if  lifting  from  the  bottom.    The  forks  should  be  set  with  a  27"  outside  spacing  so  they  fit  just  in  between  the  inverter's  4  x  4"  aluminum tube feet.   Before lifting, make sure forks are against the inside edges of both feet. ...
  • Page 13 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    Fig. 3.3 Mounting Hole Diagram (View from top of Inverter)      DOCR‐070233  Page 13 of 92...
  • Page 14: Dc Connections From The Pv Array And Ac Connections To The Grid

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4 DC Connections from the PV Array and AC Connections to the Grid    WARNING:  All electrical installations shall be performed in accordance with applicable  local, state, and national electric codes.    WARNING: Only connect the DC and AC power and grounding wires with the AC and DC  disconnect  switches  off  and  the  circuits  isolated  from  AC  power  from  the  grid  and  DC  power from the array.       WARNING:  Make sure to connect the inverter and other exposed metal equipment in  the  system  to  the  grounding  electrode  system  through  the  installation  of  the  Grounding ...
  • Page 15 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  on  both  the  AC  and  DC  points  of  entry.    GEC(s) and  EGC(s) should  be  sized  and  installed  per  the  electrical code requirements of the Area Having Jurisdiction.       DC Disconnect Switch  o Ground  Lug  –  For  DC  GEC  connection.    Depending  on  the  grounding  system  configuration, the DC ground lug may serve as the connection point for combined:   ...
  • Page 16: Ac Grounding Connections

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4.2 AC Grounding Connections  AC  grounding  connection  locations,  connection  quantity,  conductor  range,  and  terminal  torque  requirements are shown below.        AC Ground Bar  AC Ground Bar AC Ground Lug (400A AC Disco Only)          Fig. 4.1a AC Ground Connection – 200A  Fig. 4.1b AC Ground Connection – 400A  (200A Unfused AC Disconnect Switch Shown) (400A Unfused AC Disconnect Switch Shown)       AC Disconnect  AC Ground  Max Number of  Switch Type*  Connection  Connections  Conductor Range ...
  • Page 17: Dc Grounding Connections

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4.3 DC Grounding Connections  DC  grounding  connection  locations,  connection  quantity,  conductor  range,  and  terminal  torque  requirements are shown below.      DC Ground Lug  DC Ground Bar      Fig. 4.2 DC Ground Connection   (600A DC Disconnect Switch w/ DC Breakers Shown)       DC Disconnect  DC Ground  Max Number of  Switch Type*  Connection  Connections  Conductor Range  Torque  4  14 ‐ 1/0 AWG  Ground Bar  40 in‐lbs  400A  1 ...
  • Page 18: Ac Power Connections

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4.4 AC Power Connections    NOTE:  Each AC lug is designed for single conductor use only.  Where multiple lugs per  phase are provided, each lug is designed for single conductor use only.     NOTE:  Note that each inverter power rating is offered with the option of either a fused  or unfused AC disconnect switch.  The installer should refer to the current requirements  for  the  specific  inverter  power  rating,  AC  voltage,  and  disconnect  switch  type  (fused/unfused) to determine the appropriate wire sizes.    NOTE:  The phase rotation of the grid connections to the inverter must follow the L1/A,  L2/B and L3/C clockwise order.      NOTE:  When a fused AC disconnect switch is not provided, overcurrent protection of AC  power  output  cables  shall  be  provided  by  others  according  to  local,  state,  and  national  code requirements.  ...
  • Page 19: Ac Cable Entry

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  AC Cable Entry  The AC cable entry location depends on the AC disconnect switch current rating and orientation  (side facing or forward facing).  Use the following tables to determine which disconnect switch  your inverter uses, and then refer to the customer interface drawing (DOCR‐070190) for AC cable  entry locations.    AC Voltage Drop  AC  voltage  drop  should  be  minimized  to  avoid  nuisance  tripping  resulting  from  increased  AC  voltage  seen  at  the  inverter’s  output  terminals  as  the  inverter  feeds  current  into  the  grid.   Minimizing AC voltage drop also results in higher system efficiency.  An AC voltage drop of less  than 1% is recommended. ...
  • Page 20 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  The  table  below  pertains  to  the  standard  AC  disconnect  switches  without  fuses.    It  includes  requirements  for  the  AC  conductor  size,  the  number  of  terminals  available,  proper  terminal  torque, and AC disconnect switch current ratings for all PVI 50‐100KW inverter models.  The PE  models use the same AC disconnect switches as the standard models.    INVERTER MODEL  DISCONNECT  AC  TERMINALS  TERMINAL  With Unfused AC  WIRE GAUGE ...
  • Page 21 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  The  table  below  pertains  to  the  optional  AC  disconnect  switches  with  fuses.    It  includes  requirements  for  the  AC  conductor  size,  the  number  of  terminals  available,  proper  terminal  torque, and AC fuse and disconnect switch current ratings for all PVI 50‐100KW inverter models.   The PE models use the same AC disconnect switches as the standard models.    AMPERAGE  INVERTER MODEL With  AC  OF  TERMINALS  TERMINAL  DISCONNECT ...
  • Page 22: Neutral Kit Option

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Neutral Kit Option  A  neutral  is  not  required  for  proper  inverter  operation;  hence,  the  inverter  is  most  often  connected  as  a  3‐wire  system  with  no  connection  point  for  a  neutral  conductor.    For  the  interconnection of the inverter as a 4‐wire system, a neutral kit option is available.  As shown in  Figure  4.5,  the  kit  includes  a  factory  installed  neutral  lug  inside  the  AC  disconnect  switch  to  connect a neutral conductor.  When configured with the neutral kit, a jumper from the neutral ...
  • Page 23: Ac Ground Fault Detection

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    AC  NO. OF  TERMINAL  DISCONNECT  NEUTRAL  WIRE GAUGE  TORQUE  SWITCH TYPE  CONDUCTORS  200A  1  6AWG ‐ 250kcmil  275 in‐lbs  3  6AWG ‐ 250kcmil  275 in‐lbs  400A  1/0AWG ‐ 750kcmil  1 or  500 in‐lbs  2  1/0AWG ‐ 300kcmil      *See Tables 4.3 & 4.4 to determine the AC disconnect switch type by inverter model.   Table 4.5 – AC Neutral Conductor Sizes & Torques     4.5 AC Ground Fault Detection  The PVI series of inverters are not equipped with AC ground fault protection. When AC ground  fault  protection  is  used  on  the  onsite  electrical  service,  determine  if  the  ground  fault  device  is  listed to be backfed. The inverter AC output should be connected on the supply side of the device ...
  • Page 24: Dc Power Connections

    4.6 DC Power Connections    NOTE:    The  PVI  50‐100KW  inverter  models  are  designed  for  negative‐grounded  PV  arrays  only.    Contact  Solectria  Renewables  before  you  install  a  system  with  positive‐ grounded PV arrays.    NOTE:    The  maximum  current  from  the  PV  array  must  be  below  the  rating  of  the  DC ...
  • Page 25 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Grounded Grounded  Conductor  Conductor  Connection  Connection  Ungrounded  Conductor  Connection  Ungrounded  Conductor  Connections No Subcombiner  Subcombiner with (8) 40‐60A Fuses    Grounded  Grounded Conductor   Conductor  Connection  Connection  Ungrounded  Ungrounded  Conductor  Conductor  Connections Connections  Subcombiner with (6) 70‐100A Fuses  Subcombiner with (4) 110A‐200A Fuses    Figure 4.6a DC Power Connection Locations (1 of 2)  DOCR‐070233  Page 25 of 92...
  • Page 26 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Grounded  Grounded  Conductor  Conductor  Connection  Connection Ungrounded  Conductor  Ungrounded  Conductor  Connections  Connections Subcombiner with (2) 225A‐300A Fuses  Subcombiner with (6) 40‐100A Breakers      Grounded  Grounded  Conductor  Conductor  Connection Connection Ungrounded  Conductor  Connections Ungrounded  Conductor  Connections  Subcombiner with (3) 110A‐200A Breakers  Subcombiner with (2) 225A‐300A Breakers      Figure 4.6b DC Power Connection Locations (2 of 2) DOCR‐070233  Page 26 of 92...
  • Page 27: Standard Dc Disconnect Switch

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Standard DC Disconnect Switch  The  table  below  includes  requirements  for  the  DC  conductor  size,  the  number  of  terminals  available, proper terminal torque, and DC disconnect switch current ratings for the standard DC  disconnect  switches  provided  (no  subcombiner)  on  the  PVI  50‐100KW.    The  PE  models  use  the  same DC disconnect switches as the standard models.    NOTE:  The torque is different for the grounded and ungrounded terminals on the DC  disconnect switch.    TERMINAL  TERMINAL ...
  • Page 28: Dc Breaker Subcombiner

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  DC Breaker Subcombiner  The  table  below  includes  requirements  for  the  DC  conductor  size,  the  number  of  terminals  available  and  proper  terminal  torque  for  the  fused  DC  subcombiner  options  on  the  PVI  50‐ 100KW.      NOTE:  The torque is different for the grounded and ungrounded terminals on the DC  breaker subcombiner.    NO. OF  TERMINAL  TERMINAL ...
  • Page 29 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    WARNING: If the GFDI fuse blows upon connection of one or more combined strings,  a ground fault in the array must be located and eliminated before proceeding. The DC  ground  fault  is  eliminated  when  the  GFDI  fuse  can  be  replaced  and  remains  intact.  Failure  to  obey  these  instructions  may  cause  the  grounded  conductor  to  rise  to  potentially unsafe voltage levels.    WARNING: Even when the DC disconnect switch is in the off position, the ungrounded  DC conductor leading up to the DC disconnect switch will remain energized on the PV  side as long as the PV modules are in daylight. The inverter side of the DC disconnect  switch will also remain energized after the disconnect switch has been shut off until  60 seconds after the LEDs turn off, as the DC bus capacitors in the inverter discharge.   ...
  • Page 30: Lightning And Surge Protection

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4.8 Lightning and Surge Protection  The  inverter  is  designed  with  certain  protections  against  voltage  surges  in  accordance  with  IEEE  1547.    The  DC  inputs  are  equipped  with  IEC  61643‐1/‐11  Class  II,  EN  61643‐11  Type  2  surge  protection devices (SPD).  The SPD helps protect the inverter from surges by creating a temporary  low impedance path to ground.  On the DC input, separate surge paths exist from positive (+) to  ground and negative (‐) to ground.  Each path is made by a separate insert within the SPD.  A red  indicator flag will mark that an insert requires replacement.  The SPD’s can are installed inside the  DC disconnect switch.  Added protection and proper grounding provisions will help protect against ...
  • Page 31 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  The terminal blocks are labeled 9‐13 and are wired per the picture and table below:        Location  Connection  Remote Shutdown    Terminal Block 9  Input  Remote Shutdown    Terminal Block 10  Return  Revenue Grade    Terminal Block 11  Meter (RS485A)  Revenue Grade    Terminal Block 12  Meter (RS485B)    Revenue Grade  Terminal Block 13  Meter (RS485‐Gnd)  Table 4.11 – Customer Terminal Block Definition      Remote Shutdown Wiring  The  PVI  50‐100KW  inverters  feature  a  remote  shutdown  input  to  allow  for  advanced  remote  command and control systems. The input required is an isolated 24VDC signal that is wired to the ...
  • Page 32: Commissioning The Inverter

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  5 Commissioning the Inverter   Before  commissioning,  ensure  that  the  inverter  is  properly  secured  to  the  mounting  structure  and that all power and grounding connections are made to ensure that the inverter is ready to  power up.    NOTE:  Make sure all tools, parts, etc. are removed from the inverter cabinet, DC and  AC disconnect switches, and around the vicinity of the inverter before turning on.      WARNING:  Make a final check of all AC and DC power and grounding wiring at the  inverter and within the system before turning the inverter on.    NOTE:    With  the  PV  modules  connected  and  inverter  disconnect  switches  still  off,  perform ...
  • Page 33: Operation

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    5.2 Operation  The control electronics and DSP will be active as soon as DC (PV) voltage reaches 245 VDC.  The  inverter  will  go  on‐line  with  the  utility/building  3‐phase  grid  when  the  DC  voltage  first  exceeds  400  VDC  (strike  voltage).    Next,  the  inverter  will  load  the  array,  bringing  the  DC  voltage  down  from 400 VDC. Once there is enough PV power to back‐feed the grid, the inverter will produce  power according to what is being delivered by the PV array. ...
  • Page 34: Inverter Control And Communications" In The Pvi 50-100

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6 Inverter Control and Communications” in the PVI 50‐100   Every  Solectria  Renewables  commercial  inverter  includes  a  SolrenView  gateway  integrated  into  the inverter door.  This device performs multiple functions including control, monitoring and data  logging.      From the inverter a user can configure, monitor and control the inverter using a human‐machine  interface (HMI).  This HMI consists of the LCD display, four buttons, and LED indicators for power,  ground fault, and error.               Figure 6.1 – SolrenView Gateway HMI (Front)        DOCR‐070233  Page 34 of 92...
  • Page 35 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  The back side of SolrenView gateway, which can only be physically accessed when the inverter  door  is  open,  provides  connectivity  to  data  monitoring  systems.    Solectria  Renewables’  own  SolrenView.com  data  monitoring  system  can  be  interfaced  using  Ethernet  over  twisted  pair.    Third‐party monitoring systems can be connected to the inverter using Modbus RTU protocol (RS‐ 485.)    WARNING:  SolrenView  gateway  connections  must  be  made  by  qualified  personnel ...
  • Page 36: Led Indicators

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  LED Indicators  The LED indicators mounted on the front left of the inverter enclosure just above the LCD screen  allow the installer and user to see the current status of the inverter.    CAUTION Power RISK OF ELECTRICAL SHOCK NORMALLY Ground Fault GROUNDED CONDUCTORS MAY BE UNGROUNDED AND ENERGIZED Error WHEN A GROUND FAULT IS INDICATED     Figure 6.3 – LED Indicators at Normal Status      The basic LED indicator statuses are as follows:      For other LED indications please contact Solectria Renewables Customer Support.      DOCR‐070233  Page 36 of 92...
  • Page 37: Button Descriptions

      PVI 50‐100KW Series Inverters    WARNING:  If  the  yellow  Ground  Fault  indicator  is  lit  then  normally  grounded  conductors may be ungrounded and energized.  Do not touch the inverter as there  is a risk of electrical shock.  For maintenance, please contact Solectria Renewables  or  an  authorized  installer  by  visiting  http://www.solectria.com  or  by  calling  +1‐   978‐683‐9700.    6.1 Button Descriptions    The  SolrenView  HMI  is  controlled  by  four  buttons  that  are  integrated  into  the  inverter  door.  ...
  • Page 38: Main Display

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.2 Main Display       Figure 6.4 Main Display    During normal inverter operation the Main Display shows AC Energy (Eac) and AC Power (Pac).    The display updates every few seconds with new data from the inverter.  Units are dynamically  displayed based on the energy and power levels.    6.3 Accessing the Menu  From the Main Display press the ENTER button to access the menu.      Figure 6.5 Main Menu  DOCR‐070233  Page 38 of 92...
  • Page 39: Navigating The Menu Structure

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.4 Navigating the Menu Structure    The Main Menu allows the user to configure, monitor and control inverter functions.    The selected menu option is shown with an arrow on the left.  Please note that the display only  shows two menu options at a time and will scroll to show the other options.        Press the DOWN or UP button to change the selected menu option, as indicated by the arrow.        Press the ENTER button to activate the selected function or submenu.      Hint:  All menus wrap around.  Pressing the UP button when the at the top of a menu will select  the bottom‐most menu option.  Pressing the DOWN button when at the bottom of a menu will  select the top‐most menu option.    DOCR‐070233  Page 39 of 92...
  • Page 40: Displaying Inverter Measurements

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.5 Displaying Inverter Measurements    1.   From the Main Menu select the Measurements function and then press the ENTER button.      2.  The display will show the AC Energy readout:    Figure 6.6 – Measurements Function  3.  Press the DOWN or UP buttons to display different measurement values.    4.  Press the ESCAPE button to return to the Main Menu.      DOCR‐070233  Page 40 of 92...
  • Page 41 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters      The following table summarizes the measurements available:     AC Energy          Cumulative AC Energy (kWh)    AC Power          AC Power output (W)    AC Voltage         AC Voltage, Three‐phase (V)  AC Frequency          AC Frequency (Hz)    AC Current          AC Current, Three‐phase average (A)  ...
  • Page 42: Controlling The Inverter

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.6 Controlling the Inverter    Many inverter functions can be controlled through the HMI under the Set Inverter menu option.   The power can be temporarily disabled or curtailed.  Third‐party RS‐485 Modbus settings can be  viewed and modified, including inverter id and baud rate.  Inverter AC voltage and frequency trip  settings can be viewed and modified.        The following table summarizes the control functions:   Power Disable      Temporarily disables the AC output of the inverter   Inverter ID         Serial port address/ID of the inverter Baud Rate          Serial port baud rate (19200 or 9600) Vac Very High           AC Voltage Critical High Trip Setting Vac High                    AC Voltage High Trip Settings  Vac Low                  ...
  • Page 43: Stopping And Starting The Inverter

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.7 Stopping and Starting the Inverter    WARNING:  Before  conducting  any  maintenance  or  service  on  the  PV  System  the  inverter  disconnect  switches  must  be  set  to  the  “OFF”  position  and  the  absence  of  voltage must be verified by qualified personnel.  Do not rely on HMI functions to stop  the inverter as a reset might cause the inverter to start unexpectedly.  Quick Stop and Start  The Inverter can be temporarily stopped so that it ceases to export power to the grid.  Hold down  the  ESCAPE  button  for  two  seconds  to  temporarily  stop  the  inverter  if  it  is  running.    Likewise,  hold down the ESCAPE button for two seconds to initiate inverter starting if it is stopped. ...
  • Page 44: Accessing Password Protected Functions

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.8 Accessing Password Protected Functions    Certain menu functions can only be accessed after the four digit password (or PIN) is entered  through the HMI interface.      1. Select the Set Inverter submenu from the Main Menu.      2. Select the Password function at the bottom of the Set Inverter submenu.          Hint:  This option can quickly be accessed by pressing the UP button from the top of the Set  Inverter submenu, as the menu wraps around.    3. The Password screen will appear.        4. Press the ENTER button to begin entering the default password (PIN).        5. Specify each of the four PIN digits one at a time.  Press the UP button to increment the digit.   Press the DOWN button to decrement the digit.  Press the ENTER button to accept the digit.   Press the ESCAPE button to cancel PIN entry at any point.  When the fourth digit is entered  the  PIN  entry  will  be  evaluated  and  the  “Password  Correct”  message  will  flash  if  the  PIN  is  verified. ...
  • Page 45: Changing The Inverter Password

    The  inverter  password  ensures  that  unauthorized  users  are  not  able  to  access  certain  menu  functions.    The  default  password  (0000)  should  be  changed  on  commissioning.    Please  use  a  password  that  you  can  easily  remember.    Solectria  Renewables  does  NOT  have  a  master  password to reset the unit. ...
  • Page 46: Changing Voltage And Frequency Trip Settings

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.10 Changing Voltage and Frequency Trip Settings  The inverter is designed to operate within certain voltage and frequency ranges, as specified by  the utility.  When the inverter senses that the inverter and/or grid is outside any of these ranges  the inverter ceases exporting power and disconnects from the grid.  This action is referred to as  an inverter trip.    Inverter trip settings that can be reviewed include:      Vac Very High Voltage   Vac Very High Trip Time (not changeable)   Vac High Voltage   Vac High Voltage Trip Time   Vac Low Voltage   Vac Low Voltage Trip Time   Vac Very Low Voltage   Vac Very Low Voltage Trip Time (not changeable)   Fac Low Frequency   Fac Low Frequency Trip Time    Fac Very Low Frequency (not changeable)   Fac Very Low Frequency Trip Time (not changeable)   Fac High Frequency (not changeable)      NOTE: Prior to changing trip settings, the password must be entered through the ...
  • Page 47 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  1. To change trip settings, first select Set Inverter on the Main Menu:        2. Next, select VAC Very High function on the Set Inverter submenu:        3. The VAC Very High function will be displayed.  Press ENTER to modify the setting.  The  voltage value will flash, indicating that it can be changed.  Press the DOWN and UP buttons to  change the voltage setting.           4. Press the ENTER button to accept the voltage setting change.    5. If the trip time is adjustable, it will flash to indicate that it can be changed.  Press the DOWN and UP buttons to change the trip time setting.      6. Press the ENTER button to accept the trip time setting change.    7. Press the DOWN button to step to the next trip setting (VAC High).    DOCR‐070233  Page 47 of 92...
  • Page 48 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters        8.  Repeat steps 3–6 for each trip setting to be modified.  DOCR‐070233  Page 48 of 92...
  • Page 49: Establishing Ethernet Connectivity

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.11 Establishing Ethernet Connectivity    Before  SolrenView  web‐based  monitoring  can  function  the  inverter  must  be  networked  to  the  Internet.  Customers ordering the SolrenView AIR 3G Router have network connectivity turned on  in the factory; no additional steps are required.      WARNING:  Before  conducting  any  maintenance  or  service  on  the  PV  System  the  inverter  disconnect  switches  must  be  set  to  the  “OFF”  position  and  the  absence  of  voltage must be verified by qualified personnel.  Do not rely on HMI functions to stop ...
  • Page 50: Setting Up Tcp/Ip Networking

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    NOTE: The green link and yellow activity LEDs only light when the SolrenView  gateway is powered.    6.12 Setting up TCP/IP Networking    Connection  to  the  Internet  and  to  the  SolrenView  web‐based  monitoring  service  requires  functioning  TCP/IP  protocol.    This  protocol  runs  over  twisted  pair  Ethernet  wiring  and  requires  certain  connections  to  properly  operate.    See  Section  6.11  or  details  on  establishing  Ethernet  connectivity. ...
  • Page 51 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    2. Information on the inverter will be displayed including the IP, gateway, and netmask  settings.  Press the ENTER button to hold the display on the item of interest.          In  the  above  example,  the  IP  address,  gateway  and  netmask  values  are  being  automatically being set through the DHCP service.  The exact values displayed will depend  on the configuration of the network, but typically are in one of three ranges:  10.0.0.0   –  10.255.255.255  192.168.0.0   –  192.168.255.255  172.16.0.0   –   172.31.255.255    3. If the network is working on the Ethernet protocol level, but the SolrenView is unable to  obtain settings through the DHCP service the following will typically be displayed:       ...
  • Page 52: Manually Configuring Network Settings

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  If the network is not working on the Ethernet protocol level, such as if the twisted pair Ethernet  cable is not plugged in, the following will be displayed:        6.14 Manually Configuring Network Settings    To manually configure network settings:  1.  Select Config from the Main Menu and press ENTER.      DOCR‐070233  Page 52 of 92...
  • Page 53 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  2.  Select LAN from the Config Menu and press ENTER.      3.  Select the DHCP function and press ENTER to edit this setting.    4.  Press the DOWN button to turn DHCP Mode Off and press ENTER to save this setting.      5.  The DHCP Mode setting will now show Off.      6.  Press the DOWN button to access the Static IP setting.       7. Press ENTER to modify the Static IP value.    DOCR‐070233  Page 53 of 92...
  • Page 54 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    8. Specify  each  of  the  four  octet  values  (0‐255),  one  at  a  time.    Press  the  UP  button  to  increment the octet.  Press the DOWN button to decrement the octet.  Press the ENTER  button to accept the octet.  Press the ESCAPE button to cancel entry at any point.  When  the fourth octet is entered the entry will be saved.        9. Press the DOWN button to access the Gateway setting.  Change in the same manner that  the Static IP was modified.        10.  Press the DOWN button to access the Netmask setting.  Change in the same manner that  the Static IP was modified.       ...
  • Page 55: Automatically Configuring Network Settings

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.15 Automatically Configuring Network Settings  When shipped from the factory, the SolrenView gateway uses DHCP to configure the TCP/IP  settings.  If the gateway has been changed to use static IP address the following instructions will  explain how to turn on DHCP.  To configure the SolrenView gateway to use DHCP:  1.   Select Config from the Main Menu and press ENTER.    2. Select LAN from the Config Menu and press ENTER.        DOCR‐070233  Page 55 of 92...
  • Page 56: Setting Fallback Ip Address

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  3.  Select the DHCP function and press ENTER to edit this setting.    4.  Press the DOWN button to turn DHCP Mode On and press ENTER to save this setting.    5.  The DHCP Mode setting will now show On.          6.16 Setting Fallback IP Address    When the SolrenView gateway is set to use DHCP, but is unable to acquire an IP address lease, it  will “fallback” to using a specified IP address after a few seconds.    1. To specify a fallback IP, first select Config on the Main Menu and press ENTER.            DOCR‐070233  Page 56 of 92...
  • Page 57 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  2. Select LAN from the Config Menu and press ENTER.        3. Confirm that the DHCP Mode setting shows On.  The Fallback IP is only available when  DHCP is turned on.          4. Press the Down button to show the Fallback IP setting.      5. To change the Fallback IP, press the ENTER button.        6. Specify  each  of  the  four  octet  values  (0‐255),  one  at  a  time.    Press  the  UP  button  to  increment the octet.  Press the DOWN button to decrement the octet.  Press the ENTER ...
  • Page 58 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  7. Press the DOWN button to show the Gateway IP setting.      8. To change the Gateway, press the ENTER button.    9. When DHCP is on, the Gateway can either be autodetected or manually specified.      10. To  configure  the  SolrenView  gateway  to  autodetect  the  gateway  from the  DHCP  server,  select the “Autodetect” option in using the HMI.  Autodetect is the special gateway value  of 0.0.0.0.     11. To configure the SolrenView gateway to use a manual gateway, specify each of the four  octet values (0‐255), one at a time.  Press the UP button to increment the octet.  Press the  DOWN button to decrement the octet.  Press the ENTER button to accept the octet.  Press  the  ESCAPE  button  to  cancel  entry  at  any  point.    When  the  fourth  octet  is  entered  the  entry will be saved. ...
  • Page 59: Enabling Solrenview Web-Based Monitoring

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.17 Enabling SolrenView Web‐based Monitoring    Before  SolrenView  web‐based  monitoring  can  function  the  inverter  must  be  networked  to  the  Internet, see sections 6.12 through 6.15 for more details.    As explained in section 6, data logging is one of the main functions of the SolrenView gateway.   This option is turned on with the SRV Mode setting.  Once enabled, the SolrenView gateway will  periodically update various operational values and send this data to the SolrenView web‐based  monitoring service.    If SRV Mode is turned on and the gateway is unable to transfer data to the monitoring service  then  data  will  accumulate  in  a  queue  on  the  SolrenView  gateway.    This  queue  is  stored  in  non‐volatile ...
  • Page 60: Viewing And Setting The Date/Time

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  2. Next, select SRV Mode function on the Config Menu and press ENTER:        3. The SRV Monitoring function will be displayed.  Press ENTER to modify the setting.    Press the DOWN button to change the setting to On.          4. Press the ENTER button to accept the setting change.     6.18 Viewing and setting the Date/Time    When the SolrenView web‐based monitoring service is purchased and functioning, it is normally  not necessary to set or maintain the time on the inverter.  The time will automatically be set and  adjusted based on the inverter’s time‐zone.      NOTE: The date is only editable if SRV Mode is off.    DOCR‐070233  Page 60 of 92...
  • Page 61 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  To view the date and time:    1. First select Config on the Main Menu and press ENTER.          2. Select the Date/Time option on the Config Menu and press ENTER.        3. The current date will be displayed.  If the date can be modified an arrow will appear just  before the month.  Note:  The date is only editable if SRV Mode is off.  When SRV Mode is  on, the date and time is automatically set.            DOCR‐070233  Page 61 of 92...
  • Page 62 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  4. Press the ENTER button to begin changing the date.   The month will flash, indicating that  this  portion  of  the  date  can  be  changed  with  the  buttons.    Press  the  UP  button  to  increment the month and the DOWN button to decrement the month.  Press the ENTER  button to accept the month.  Press the ESCAPE button to cancel and return to the menu.   5. The  day  will  flash,  indicating  that  this  portion  of  the  date  can  be  changed  with  the  buttons.  Press the UP button to increment the day of the month and the DOWN button ...
  • Page 63: Rebooting The Solrenview Gateway

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.19 Rebooting the SolrenView Gateway  If the SolrenView Gateway cannot communicate over the Internet or is not updating inverter data  it may need to be rebooted.  To reboot SolrenView gateway:    1. First select Config on the Main Menu and press ENTER:    2. Select the Reboot option from the menu and press ENTER.       3. The Reboot monitor prompt will be shown.  Press the ENTER button to reboot the  SolrenView gateway.        DOCR‐070233  Page 63 of 92...
  • Page 64: Resetting The Solrenview Gateway To Factory Defaults

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.20 Resetting the SolrenView Gateway to Factory Defaults    It may be necessary to reset the SolrenView gateway to factory defaults.  This does not reset the  inverter core, nor shutdown the inverter for any period of time.    NOTE: Resetting the SolrenView gateway will also clear events, revenue‐grade KYZ  counters and SolrenView.com data queue.  Caution should be used with this  function to avoid data loss.    To reset the SolrenView gateway:    1. First select Config on the Main Menu and press ENTER.      2. Select the Reset All option from the menu and press ENTER.       DOCR‐070233  Page 64 of 92...
  • Page 65: Inverter Counts And Logs

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  3.  A message warning that the SolrenView gateway is about to be set to factory defaults is  shown.  Press the ESCAPE button to cancel the reset.        4.  Select the Yes option under Clear settings to reset the SolrenView gateway to factory  defaults.  The Reset Storage screen will appear for a moment.          6.21 Inverter Counts and Logs    The inverter keeps track of various events and errors through error logging and cumulative  counters.    Error logs are a record of events (changes of state), with the earliest event shown first.  There are  a total of 30 log entries available and newer entries overwrite older entries.  Each entry in the log  is time stamped in MM/DD/YY format.    Error counts display cumulative counters for each supported event/error, with the highest error  count shown first.    DOCR‐070233  Page 65 of 92...
  • Page 66: Displaying Error Counts

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.22 Displaying Error Counts    1. Select Inv Events from the Main Menu and press ENTER.         2.  Select Err Counts from the Inv Events Menu and press ENTER.            DOCR‐070233  Page 66 of 92...
  • Page 67 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  3. The Error Counts are displayed in order of occurrence, with the most frequent error  displayed at index position 1.  In this example the most frequent error is Contactor  Failure; two contactor fail events were logged with the last one logged on Jan 02, 2013 at  7:12 am.        The data format is index number, date/time and occurrences on the first line.  The second  line is the type of the event.    4. Press the DOWN button to see the next Error Count entry.  Continuing our example, the  second most frequent error is Lost Frequency lock, which occurred once on Jan 01, 2013  at 7:10 am.          5. If no Count data is recorded, the date and time that the Counts were last cleared is  displayed.          6. Press the ESCAPE button to return to the Inv Events menu.       DOCR‐070233  Page 67 of 92...
  • Page 68: Displaying Error Logs

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.23 Displaying Error Logs    1. Select Inv Events from the Main Menu and press ENTER.           2.  Select Err Logs from the Inv Events Menu and press ENTER.        DOCR‐070233  Page 68 of 92...
  • Page 69 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  3. The most recent Error Log entries is displayed at index position 1.        The data format is index number, date/time and event state on the first line.  When the  Error first is asserted the event state is shown as “On”.  When the Error ceases the event  state is shown as “Off”.  The second line is the type of the event.    4. Press the DOWN buttons to see the next event stored in the log.          In this example, the inverter asserted a Lost Freq Lock error on Jan 01, 2013 at 7:10 am  and ceased to assert the Lost Freq Lock error on Jan 01, 2013 at 7:11 am.    5. If no Events are recorded, the date and time that the Events were last cleared is displayed.        6. Press the ESCAPE button to return to the Inv Events menu.       Hint:  Press the UP button from Error log index 1 to see the most recent Error logged.    DOCR‐070233  Page 69 of 92...
  • Page 70: Clearing Error Counts Or The Log

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.24 Clearing Error Counts or the Log    1. Select Inv Events from the Main Menu and press ENTER.         2. Select Clear from the Inv Events Menu and press ENTER.        The Clear History prompt will be shown.  Select the type of history to be cleared by  pressing the UP and DOWN buttons.  Press ENTER to clear the history based on one of  these settings.  Press the ESCAPE button to cancel.      None:    H istory is not cleared.     Err Log: Clears the Error Log only.  Err Counts: Clears the Error Counts only.  All: Clears the Error Counts and Error Log.    DOCR‐070233  Page 70 of 92...
  • Page 71 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  List of Logged Events    The following events are logged and counted:     AC Contact Open   AC Frequency High   AC Frequency Low   AC Islanding   AC Voltage High   AC Voltage Low   Contactor Err   CT Failure   DC GND FAULT   DC Voltage High   Desat Error   DMGI Overtemp   Fan Life Reached   IGBT Overtemp   Lost Freq Lock   MAG Fail   Min Vmpp Reached  ...
  • Page 72: Hmi Menu Structure

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  6.25 HMI Menu Structure      DOCR‐070233  Page 72 of 92...
  • Page 73: Troubleshooting And Maintenance

       AC Freq High acceptable limits, the inverter will restart  when frequency returns to normal range.    If possible measure the frequency or contact  The AC grid voltage is less than the    Pac:   XXXX W      local utility provider. If AC frequency is below  low limit.   AC Freq Low  acceptable limits, the inverter will restart    when frequency returns to normal range.    Turn off the inverter and contact Solectria  The AC contactor or sensing circuit    Contactor Fail      Renewables. The inverter may need to be  has failed   978‐683‐9700   serviced by an authorized service provider.    The internal current monitoring has  Turn the DC and AC off, restart the inverter.    CT Failure  The inverter may need to be inspected and  failed   978‐683‐9700  serviced by an authorized service provider. ...
  • Page 74  Waiting for grid     The VAC grid connection phasing does  Swap two of the phase wire positions at the   Reverse phasing  inverter AC wiring terminals in the AC  not match the inverter’s phasing   & restart PVI!  disconnect switch, then restart     The inverter will hold the DC voltage at this  The power point tracking has been   Pac:   XXXX W    level until Vmpp increases.  reached   Min Vmpp reached    The AC contactor is open when it is being  Turn off the inverter and contact Solectria    AC Contact Open    commanded to be closed Renewables. The inverter may need to be   978‐683‐9700   serviced by an authorized service provider.    Turn off the inverter and contact Solectria  An internal failure of the voltage   Vsense Err    Renewables. The inverter may need to be  sensing circuit has occurred   978‐683‐9700    ...
  • Page 75: Troubleshooting

      Before  attempting  to  troubleshoot  the  inverter,  please  read  the  entire  manual.       Steps to Perform when PV system not functioning:   Check inverter LED indicator status and LCD screen for inverter status and error messages   Check to ensure that inverter is connected to AC power    Check for clockwise phase rotation of AC power connections   Check to ensure that DC (PV) input is connected     Verify proper polarity of DC (PV) positive (+) and negative (‐) input pairs   Verify PV string Maximum Power Point Voltage at design high temperature and PV string  Open Circuit Voltage at design low temperature is compatible with inverter input voltage  specifications.     Contact installer or Solectria Renewables if malfunction persists      If contacting Solectria Renewables for assistance, please provide:  1. Inverter Model Number/Part Number  2. Inverter Serial Numbers  3. Short Description of Problem (LCD messages, when problem started, how often problem  occurs, under what conditions the problem occurs)   4. Design Information (PV modules, string sizing, output power, short‐circuit current and  open circuit voltage string layout)  See Appendix for Solectria contact information.     ...
  • Page 76: Preventative Maintenance

    Check the fan and make sure it spins freely.  o See Section 7.4 about turning the inverter off before performing this service.   No grid sensing:  o Grid sensing fuses blown (1A AC or as labeled) inside the main enclosure.  Contact  Solectria  Renewables  (Do  not  replace  fuses,  as  this  represents  an  abnormal  failure).   No  LED  indications  when  the  sun  is  shining.    If  the  grid  voltage  and  DC  (PV)  voltage  is  present and no response from inverter is evident: ...
  • Page 77: Intake Louver Vent Cleaning

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    A harsh environment is defined as any of the following conditions:  Excessive temperature either hot or cold    In a desert area with sand or other debris constantly in contact with the inverter   In an area with excessive pollen or dust  Indoors if located in a manufacturing area with airborne particles   Coastal regions exposed to salt water  7.4 Intake Louver Vent Cleaning  WARNING:  The intake louver vent can be cleaned only when the inverter is off, both  DC and AC Disconnect switches off and completely locked and tagged out. Absence of  dangerous voltages must be verified by qualified personnel before performing any  service.    Intake  louver  vent  cleaning  is  recommended  at  the  intervals  specified  in  Section  7.3.    Consider  cleaning  intake  louver  vent  during  the  early  morning  or  late  evening  so  little  or  no  energy  generation is lost. ...
  • Page 78 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  Opening the Main Enclosure    WARNING:  The enclosure can only be opened when the inverter is off, both DC and AC  Disconnect switches off and completely locked and tagged out. Absence of dangerous  voltages must be verified by qualified personnel before performing any service.    Use the SolrenView HMI keypad to temporarily disable the power output by pressing and  holding the ESCAPE button for two seconds.   Switch off DC disconnect switch  Switch off AC disconnect switch   Watch until all LED indicators have been off for 60 seconds to allow capacitors to discharge  Open handle on door (use key if locked)    Before closing the main enclosure always check for any signs of problems such as corrosion, loose  parts, insect or animal infestation, excessive dirt/dust or over heated or deformed/aged‐looking  parts.      Opening the DC Disconnect Switch Enclosure    WARNING:  DC Input wiring from the array may be energized even with inverter off  and DC Disconnect Switch open.      Disconnect inverter from DC power from array to ensure that live DC is not entering DC  disconnect switch enclosure.   Use the SolrenView HMI keypad to temporarily disable the power output by pressing and  holding the ESCAPE button for two seconds.   Switch off DC disconnect switch  Switch off AC disconnect switch  Watch until all LED indicators have been off for 60 seconds to allow capacitors to discharge  Remove DC disconnect switch cover door retention screws     Opening the AC Disconnect Switch Enclosure    WARNING:   AC output  wiring leaving the AC  Disconnect  Switch Enclosure to point  of  interconnect may be energized even with inverter off and AC Disconnect switch open.  ...
  • Page 79: Fuse Replacements

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  7.6 Fuse replacements  AC Fuses (if equipped)    WARNING: If inverter is equipped with the fused AC disconnect switch, fuses must only  be replaced with 600VAC rated fuses of the same type and rating.    The following table includes current ratings of fuses provided with fused AC disconnect switch  option according to inverter power rating and AC output voltage.      Inverter Model  AC Voltage  PVI‐50KW  PVI‐60KW  PVI‐75KW  PVI‐85KW  PVI‐100KW  PVI‐75KW‐PE  PVI‐85KW‐PE  PVI‐100KW‐PE  208V  175A  225A  300A  300A  350A  240V  150A  200A  225A  300A  300A  480V  110A  110A  125A  150A ...
  • Page 80: Warranty Policy

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  7.7 Warranty Policy    Solectria Renewables Warranty Coverage:  Solectria Renewables Limited Warranties are provided by Solectria Renewables, LLC. ("Solectria  Renewables") and cover defects in workmanship and materials. Solectria Renewables’ price for  the products is based on inclusion of these limited warranty provisions and disclaimers. In the  event of a conflict between the terms of this Limited Warranty and any terms and conditions  proposed by purchasers of Solectria Renewables’ products, these Limited Warranty provisions  shall govern the parties’ obligations with respect to warranty coverage for defective products.    Warranty Registration:  To register the product, please enter the following information at:  http://www.solectria.com/registration     Duration of a Solectria Renewables Warranty Period:  For three‐phase inverters (PVI 10kW and higher) and for the PVI 1800 and PVI 2500 inverters, the  warranty period is 60 months from the date of purchase of the inverter by the end user or 64  months after the delivery date from Solectria Renewables to the distributor or the dealer /  installer, whichever is shorter. If a warranty extension has been purchased, the term is defined as  an extension beyond 60 months. For example, if a 5 year extension (to 10 years total) is  purchased, the term becomes 120 months from date of purchase. For the PVI 3000 to PVI 7500  inverters, the warranty period is 120 months from the date of purchase by the end user or 124  months after the delivery date from Solectria Renewables to the distributor or the dealer /  installer, whichever is shorter.     If Solectria Renewables repairs or replaces a product, its warranty continues for the remaining  portion of the original Warranty Period or 90 days from the date of the repair/replacement  shipment to the customer, whichever is greater.    Solectria Renewables’ obligation to repair or replace a defective product under this warranty is  contingent upon Solectria Renewables receiving full and timely payment for the warranted  products and associated shipping charges. Solectria Renewables Warranty Coverage is voidable,  at Solectria Renewables’ sole option, if full payment for products and associated shipping charges  are not received in full and in a timely manner by Solectria Renewables. Please contact Solectria  Renewables Customer Service for further details on other products.   ...
  • Page 81 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  What will Solectria Renewables do?    Solectria Renewables will, at its sole option, repair or replace the defective product free of  charge, provided that Solectria Renewables is notified of the product defect within the Warranty  Period for the product, and provided that Solectria Renewables, through inspection, establishes  the existence of such a defect and that it is covered by the Limited Warranty.  Solectria Renewables will, at its sole option, use new and / or reconditioned parts in performing  warranty repair and/or replacements. Solectria Renewables reserves the right to use parts or  products of original or improved design in the repair or replacement of the product. All replaced  products and all parts removed from repaired products become the property of Solectria  Renewables. Solectria Renewables will attempt to repair the unit within a reasonable time  period. No provision will be made for reimbursement of lost energy production.  For three‐phase inverters 10kW and higher:  Solectria Renewables covers parts, travel and labor necessary to repair the product and shipment  of parts to and from the customer via a Solectria Renewables‐selected non‐expedited surface  freight within the contiguous United States, Canada and Mexico. For Alaska, Hawaii and all other  installation locations Solectria Renewables will supply necessary parts as needed for warranty  repairs; however, travel is not included. Contact Solectria Renewables customer service for  details on the freight policy for return shipments outside of the contiguous United States, Canada  and Mexico.  Obtaining Service:    If your product requires troubleshooting or warranty service, contact your distributor or dealer /  installer. If you are unable to contact your distributor or dealer / installer, or the distributor or  dealer / installer is unable to provide service, contact Solectria Renewables directly at the  number listed on the website in the customer service section for your product.  Solectria Renewables may send personnel to a jobsite or contract with an area technician,  installer or other authorized, trained service personnel to service / replace components.  Reimbursement for contracted services: Solectria Renewables will submit a purchase order to the  designated service personnel before work is performed. This purchase order will cover time  expected for the required service and most likely an allocation for travel time.  Direct returns may be performed according to the Solectria Renewables Return Material  Authorization Policy.  In any warranty claim, dated proof of purchase must accompany the product and the product  must not have been disassembled or modified without prior written authorization by Solectria  Renewables.   ...
  • Page 82 ‐ The dated invoice or purchase receipt showing the product exchanged under warranty.  Solectria Renewables provides technical assistance Monday‐Friday, 8:30am‐7pm EST and on‐ call  technical support is provided outside normal business hours.   What does the Solectria Renewables warranty not cover?    Solectria Renewables Limited Warranties do not cover normal wear and tear of the product or  costs related to the removal, installation, or troubleshooting of the customer's electrical systems.  These warranties do not apply to and Solectria Renewables will not be responsible for any defect  in or damage to:  a) The product, if it has been misused, neglected, improperly installed, physically damaged  or altered, either internally or externally, or damaged from improper use or use in an  unsuitable environment;  b) The product, if it has been subjected to fire, water, generalized corrosion, biological  infestations, acts of God or input voltage that creates operating conditions beyond the  maximum or minimum limits listed in the Solectria Renewables product specifications  including high input voltage from generators or lightning strikes;  c) The product, if repairs have been made to it other than by Solectria Renewables or its  authorized, trained service personnel;  d) The product, if it is used as a component part of a product expressly warranted by  another manufacturer;  e) The product, if its original identification (trademark, serial number) markings have been  defaced, altered, or removed;  f) The product, if it has been damaged in shipping (unless approved in writing by Solectria  Renewables);  g) Any installation and operation beyond the scope covered by relevant safety regulations  (UL1741, NFPA 70, etc.);  h) Third party monitoring equipment.   i) Failure to perform Preventative Maintenance may void the warranty.  DOCR‐070233  Page 82 of 92...
  • Page 83 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters      DISCLAIMER    SOLECTRIA RENEWABLES LIMITED WARRANTIES ARE THE SOLE AND EXCLUSIVE WARRANTY  PROVIDED BY SOLECTRIA RENEWABLES IN CONNECTION WITH YOUR SOLECTRIA RENEWABLES  PRODUCT AND ARE, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES,  CONDITIONS, GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR  IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER  ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S  LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT  RESTRICTION ANY IMPLIED WARRANTY OF MERCHANTABILITY OR CONDITION OR QUALITY OF  THE PRODUCT, ANY IMPLIED WARRRANTY OF FITNESS FOR A PARTICULAR PURPOSE, OR ANY  IMPLIED WARRANTY OF DISTRIBUTOR OR DEALER/INSTALLER ABILITY, ALL OF WHICH ARE  EXPRESSLY DISCLAIMED TO THE FULLEST EXTENT PERMITED BY LAW.     ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,  OR ANY IMPLIED WARRANTY OF DISTRIBUTOR OR DEALER / INSTALLER ABILITY, TO THE  EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT, SHALL BE LIMITED IN  DURATION TO THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY, TO THE FULLEST  EXTENT PERMITTED BY LAW.    IN NO EVENT WILL SOLECTRIA RENEWABLES, INCLUDING ITS SUPPLIERS, MANUFACTURERS,  VENDORS, SUBCONTRACTORS, DISTRIBUTORS, DEALERS AND ANY OTHER AFFILIATES BE LIABLE  FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, LOSSES,  COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING  WITHOUT RESTRICTION ANY ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO  PROPERTY, INCLUDING LOSS OF USE AND INTANGIBLE HARM OF ANY KIND, AND ANY PHYSICAL  DAMAGE OR OTHER DAMAGE ARISING FROM OR AS A RESULT OF ANY USE, MISUSE OR ABUSE  OF THE PRODUCT, OR THE INSTALLATION, INTEGRATION OR OPERATION OF THE PRODUCT,  REGARDLESS OF WHETHER SUCH INSTALLATION, INTEGRATION OR OPERATION WAS  PERFORMED PROPERLY OR IMPROPERLY.    Solectria Renewables neither assumes nor authorizes any other person to assume for it any other  liability in connection with the repair or replacement of the Product.    Exclusions of the Policy: ...
  • Page 84 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters    WITHOUT LIMITING THE GENERALITY OF THE FOREGOING, UNLESS SPECIFICALLY AGREED TO BY  IT IN WRITING, SOLECTRIA RENEWABLES    (a)  MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF  ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN MANUALS OR OTHER  DOCUMENTATION PROVIDED BY IT IN CONNECTION WITH THE PRODUCT; AND    (b)  ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR  EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL,  WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION.  THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS’ RISK.    WARNING: LIMITATIONS ON USE    Please refer to your product user manual for limitations on uses of the product. Specifically,  please note that Solectria Renewables’ products are not intended for use in connection with life  support systems and Solectria Renewables makes no warranty or representation in connection  with any use of the product for such purposes.    DOCR‐070233  Page 84 of 92...
  • Page 85: Return Material Authorization Policy

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  7.8 Return Material Authorization Policy     Please review our Return Merchandise Authorization Policy below.    Obtaining a required, Return Material Authorization:  Before returning a product directly to Solectria Renewables you must obtain a Return Material  Authorization (RMA) number and the correct factory "Ship To" address. Products must also be  shipped prepaid. Product shipments will be refused and returned at your expense if they are  unauthorized, returned without an RMA number clearly marked on the outside of the shipping  box, if they are shipped collect, or if they are shipped to the wrong location.    Information Solectria Renewables needs when you are obtaining service:   1) The model names and serial number of your product     Preparing the product for shipping:  1)  Package the unit safely, preferably using the original box and packing materials. Please  ensure that your product is shipped fully insured in the original packaging or equivalent. This  warranty will not apply where the product is damaged due to improper packaging.  2)  Include the following:  The RMA number supplied by Solectria Renewables clearly marked on the outside  of the box.  A return address to which the unit can be shipped. Post office boxes are not                                      acceptable.  A contact telephone number where you can be reached during work hours.  A brief description of the problem.    Ship the unit prepaid to the address provided by your Solectria Renewables’ customer service  representative.    Returning a product from outside of the USA or Canada:  In addition to the above, you MUST include return freight funds and are fully responsible for all  documents, duties, tariffs, and deposits.     Contact information: ...
  • Page 86: Technical Data

    The  highest  open  circuit  voltage  occurs  when  the  PV  modules  are  at  the  coldest temperature and in bright sun.     Because  the  PV  modules  also  have  a  reduction  in  voltage  at  high  cell  temperatures,  you  must  make sure the MPPT voltage of the strings will not drop below the minimum inverter DC input  voltage in hot temperature conditions.    Both the maximum open circuit voltage (OCV) when at maximum cold temperatures and  minimum MPPT voltage when at maximum hot temperatures can be calculated for a PV module  using its specification sheet. PV module string sizing can then be used to determine how many  modules can be used in a string. Visit http://www.solectria.com/?page_id=30 to use Solectria  Renewables’ interactive string sizing tool.    8.1 Input DC (PV) Specifications    PVI 75KW PVI 85KW  PVI100KW   PVI 50KW ...
  • Page 87: Output Ac Specifications

    Break load rated, NEMA 3R, Breaks Ungrounded Conductor  DC Disconnect Voltage Rating  DC Disconnect Current Rating  400A or 600A, Varies by model, see Table 4.6    *Low Voltage (LV) Units are not ETL listed, contact Solectria for availability  Table 8.1 – DC Input Specifications    8.2 Output AC Specifications  The  inverters  are  designed  to  feed  power  into  a  standard  60Hz,  three‐phase  AC  utility  service  provided  within  a  facility  by  a  transformer  with  a  rating  of  not  less  than  the  rating  of  the ...
  • Page 88: Other Specifications

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters      Factory Default  Adjustment Range  ANSI  Device  Voltage Limit Clearing Time Voltage Limit  Clearing Time Trip Setting  Number  (p.u.)  (s)  (p.u.)  (s)  Undervoltage (fast)  27  V < 0.5  0.16  V < {0.5, fixed}  0.16  Undervoltage (slow)  27  V < 0.88  2.00  V < {0.5 to 1.0}  0.16 to 300  Overvoltage (slow)  59  V > 1.1  1.00  V > {1.1 to 1.2}  0.16 to 300  Overvoltage (fast)  59  V > 1.2  0.16 ...
  • Page 89 Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  MPPT Min.    (Standard)    MPPT Min.   (LV Option)  Strike Voltage (Standard)   Strike Voltage (LV Option)        Figure 8.1 AC Output Power vs. DC Input Voltage of PVI 50‐100KW Series Inverters  DOCR‐070233  Page 89 of 92...
  • Page 90: Internal Circuit Diagram

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  8.4 Internal Circuit Diagram  The basic power flow within the PVI 50KW‐100KW series inverters is shown in the simplified one‐ line diagram below.  Note that grounding and GFDI circuit is not depicted.    Figure 8.2 – Simplified One‐Line Diagram of PVI 50‐100KW Series Inverters    DOCR‐070233  Page 90 of 92...
  • Page 91: Appendices

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  9 Appendices  9.1 Appendix A – PVI 50KW, 60KW, 75KW, 85KW, 100KW Data Sheet    http://www.solectria.com/datasheets/PVI_50‐100KW_Datasheet.pdf 9.2  Appendix B – String Sizing Tool  http://www.solectria.com/?page_id=30  9.3 Appendix C – Contact Information Solectria Renewables LLC  360 Merrimack Street  Building 9, 2  floor  Lawrence, Massachusetts 01843  USA  Tel:      978.683.9700  Fax:       978.683.9702  Sales/General Info:   inverters@solectria.com  Customer Support:   service@solectria.com  Website:    www.solectria.com  9.4 Appendix D – Authorized Distributors  See website for complete and updated listing: www.solectria.com   DOCR‐070233  Page 91 of 92...
  • Page 92: Appendix E - Ul1741/Ieee 1547 Authorization Letter To Mark Product

    Installation and Operation Manual (Rev A)    PVI 50‐100KW Series Inverters  9.5 Appendix E – UL1741/IEEE 1547 Authorization Letter to Mark Product  DOCR‐070233  Page 92 of 92...

This manual is also suitable for:

Pvi 60kwPvi 75kwPvi 85kwPvi 100kw

Table of Contents