Once there is enough PV power at 205V DC to back feed 3-phase AC, power switching will
automatically feed power to the grid.
Operating states, GFDI status and error indications shown by the LED indicators, which are
described in the next sections.
4 – Power, GFDI and Error LED Indicators and LCD display
4.1 Power, GFDI and Error LED Indicators
The LED indicators mounted on the right-hand side of the enclosure just above the DC disconnect give
the user a quick look at what state the inverter is in and if it is operating normally.
GREEN – indicates "power", the unit is powered up and / or feeding power to the grid
RED – "ERROR" or "FAULT", the inverter is not providing power due to an error or fault
RED & YELLOW – indicate that a ground fault has been detected and it must be located before the
inverter will function. Check GFDI fuse if RED LED remains solid.
NOTE: If the GFDI fuse is blown, see "Opening the Main Enclosure" and Fig. 6,
"Description and Location of Components". Turn off AC & DC power and locate, check
and replace the GFDI fuse with a 3/4A midget fuse 500V DC or 600V DC rated such as
Solectria Renewables P/N KLK ¾ or KLKD 3/4, or Bussmann, KLK-3/4 or KLKD-3/4.
Description of LED symbols used to indicate LED status in this manual
LED Off
LED flashing (25% on, 75% off)
LED on once per second
LED on two times per second
LED on with short interruptions (75% on, 25% off)
LED on
DOCR-060002 rev30