Solectria Renewables PVI 10kW Installation And Operation Manual page 32

208, 240 and 480vac commercial, grid-tied photovoltaic inverter
Table of Contents

Advertisement

PVI 10kW / PVI 13kW / PVI 15kW
Output (AC) specifications for PVI 10KW / PVI 13KW / PVI 15KW Inverter:
Nominal and Maximum output power of the PVI 10KW
Operating voltage range (+10%/- 12%)
Operating frequency range
Operating voltage range (VAC)
Over / under voltage trip points and times
Voltage measurement accuracy
Over / under frequency trip points and times
Frequency measurement accuracy
Maximum Output Current PVI 10KW
Maximum Output Current PVI 13KW
Maximum Output Current PVI 15KW
Peak short circuit output current
Total Harmonic distortion (THD)
(@ full power)
Power Factor
Anti-islanding protection
AC disconnect, 3-phase
Over current protection
Short circuit protection
Surge test
Inverter peak Efficiency
Other specifications:
DC combiner-fuse enclosure
(Optional)
DC Disconnect (Integral)
Ambient Temperature
Storage Temperature
DOCR-060002 rev30
of the PVI 13KW
of the PVI 15KW
208VAC
240VAC
59.3 to 60.5 Hz
183 - 228
211 - 264
per IEEE Std. 1547-2003, Table 1
+/- 2%
per IEEE Std 1547-2003, Table 2
28 A
24A
37 A
32A
42 A
37A
per UL 1741, IEEE 1547
per UL1741 / IEEE1547
per UL1741 / IEEE1547
8/10/12/15A fuses available
5-7 pole, NEMA 3R, TVSS
Break load rated, NEMA 3R
32
Installation and Operation Manual
10.0 kW AC
13.2 kW AC
15.0 kW AC
480VAC
423 – 528
+/- 0.1 Hz
12 A
16 A
18 A
75 A
< 4%
> 95%
included
inverter limited
94.8%
o
o
-25
to 50
C
o
o
-25
to 50
C
July 7, 2010

Advertisement

Table of Contents
loading