NOTE: When using an external analog (0 -10 V) or 2 wire modulation input, the factory
default 03should be changed to 00.
Parameter H factory set must not be changed
6.6.10 DHW control stop set point (I)
Adjustable from 00 - 30 °C factory default 20°C.
Refer to Par. 6.6.7.
6.6.11 DHW control option (J)
Three options 00 - 01 - 02 factory default 00.
This value sets the DHW control option.
00 Three way diverting valve (port A - HTG and Port B - DHW)
01 DHW pump
02 Inverted three way diverting valve (port B - HTG and Port A - DHW)
Parameter L not applicable
6.6.12 HTG cut in temp (N)
Adjustable 1) (-10) to 20 °C, factory default 03.
This value sets the ∆T below actual return temp at the moment of control stop during
HTG demand.
A control stop occurs when the flow temp equals the flow temp set point + 5°C.
HTG cut in temperature = actual return temperature at the moment of control stop
(e.g. 60) - parameter N (3)
ie 60 - 3 = 57°C
If this takes longer than the maximum delay time (parameter U), the boiler will restart
(unless flow temperature exceeds flow temperature setpoint).
Parameter O not applicable
6.6.13 Boiler type (P)
Factory default 80 must not be changed.
Parameter T factory set must not be changed.
6.6.14 Maximum delay time (U)
Adjustable from 00 - 99 minutes, factory default 15 minutes (15).
This value sets the maximum off time following a control stop. The minimum off time is
preset to a fixed value (150 sec.).
A combination of both values is used to prevent hunting taking place.
27