Chapter 8
1. Find the rack-mounting template.
If your HP NetServer is still in its box, the template should be in the
accessories tray that sits on top of the NetServer itself.
2. Hold the template alongside the outside face (front) of the left front rack
columns.
3. Line up the bottom of the template with the lower line of the NetServer's
location in the rack.
The template covers a span of 5 EIA units, which is the height requirement
of the HP NetServer.
4. Use the marking pen to mark the 2nd and 14th holes on both front
columns, as shown on the template. See Figure 8-3.
NOTE
The two column adapters are mounted at the 2nd and 14th
holes on the respective front column and provide the captive
nuts for mounting the rack slides to the front columns at 7th
and 9th holes from the bottom. If you don't have the template,
Figure 8-3 shows the location on the front columns for the
column adapters.
Figure 8-2. Placing Rack Nuts on Rack Columns
Rack-Mounting the HP NetServer