Table 3-1
Available Power Options
Source
Option
Type
6
3-phase
7
3-phase
a. A dedicated branch circuit is required for each PDCA installed.
Table 3-2
Power Cord Option 6 and 7 Specifics
PDCA
Attached Power Cord
Part Number
A5201-69023
OLFLEX 190 (PN 600804) is a
(Option 6)
2.5 meter multi conductor,
600 V, 90°C, UL and CSA
approved, oil resistant flexible
cable. (8 AWG 60 A capacity)
A5201-69024
H07RN-F (OLFLEX PN
(Option 7)
1600130) is a 2.5 meter
heavy-duty neoprene-jacketed
harmonized European flexible
cable. (4 mm

Returning Equipment

If the equipment is found to be damaged, use the original packing material to repackage the cabinet for
shipment. If the packing material is not available, contact the local HP Sales and Support Office regarding
shipment.
Before shipping, place a tag on the container or equipment to identify the owner and the service to be
performed. Include the equipment model number and the full serial number, if applicable. The model number
and the full serial number are printed on the system information labels located at the bottom front of the
cabinet.
Chapter 3
Source Voltage
(Nominal)
Required
Voltage range 200
4-wire
to 240 V ac,
phase-to-phase,
50 Hz / 60 Hz
Voltage range 200
5-wire
to 240 V ac,
phase-to-neutral,
50 Hz / 60 Hz
2
32 A capacity)
Input Current
PDCA
Per Phase 200
to 240 V ac
44 A maximum
per phase
24 A maximum
per phase
Attached Plug
Mennekes
ME 460P9
(60 A capacity)
Mennekes
ME 532P6-14
(32 A capacity)
Installing the System
Unpacking and Inspecting the System
Power Receptacle
Required
a
Connector and plug
provided with a 2.5 m (8.2
feet) power cable.
Electrician must hard wire
receptacle to 60 A site
power.
Connector and plug
provided with a 2.5 m (8.2
feet) power cable.
Electrician must hard wire
receptacle to 32 A site
power.
Receptacle
Required
Mennekes
ME 460R9
(60 A capacity)
Mennekes
ME 532R6-1500
(32 A capacity)