Table 2-17. Physical Environmental Specifications - HP A9834-9001B User's & Service Manual

Hewlett-packard integrity superdome server user service guide
Table of Contents

Advertisement

System Specifications
Environmental Requirements
Table 2-17
Physical Environmental Specifications
Voltage
200–240 Vac
Typical
Heat
Release
Description
Watts
Minimum
Configuration
3423
Maximum
Configuration
9130
Typical
Configuration
6968
ASHRAE
Class
1
a. Derate maximum dry bulb temperature 1oC/300 m above 900 m.
b. The system deviates slightly from front to top and rear airflow protocol. Approximately 5 percent of
the system airflow is drawn in from the rear of the system. See Figure 2-2 on page 73 for more
details.
c. See Table 2-15 on page 69 and Table 2-16 on page 70 for additional details regarding minimum,
maximum, and typical configurations.
74
Condition
Maximum
Airflow,
at 32
b
Nominal
CFM
CFM
3
m
/hr
2900
5.0
2900
2900
5.0
2900
2900
5.0
2900
Minimum
Configuration
Maximum
Configuration
Typical
Configuration
Airflow,
o
a,b
C
Weight
lb
3
m
/hr
5.0
926.3
5.0
1241.2
5.0
1135.2
c
2 Cell, 4 DIMM, 2 I/O
c
8 Cell, 32 DIMM, 4 I/O
c
6 Cell, 16 DIMM, 4 I/O
Overall System
Dimensions
(W X D X H)
kg
in
mm
420.3
30x48
76.2x121.9
x77.2
x195.6
563.2
30x48
76.2x121.9
x77.2
x195.6
515.1
30x48
76.2x121.9
x77.2
x195.6
Chapter 2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Integrity superdome sx2000