Airflow; Figure 2-2. Airflow Diagram - HP A9834-9001B User's & Service Manual

Hewlett-packard integrity superdome server user service guide
Table of Contents

Advertisement

Airflow

HP Integrity Superdome/sx2000 systems require the cabinet air intake temperature to be between 15
ο
ο
ο
32
C (59
F and 89.6
F) at 2900 CFM.
Figure 2-2 illustrates the location of the inlet and outlet air ducts on a single cabinet.
NOTE
Approximately 5 percent of the system airflow is drawn from the rear of the system and exits
the top of the system.
Figure 2-2
Airflow Diagram
Airflow exit (300 CFM)
A thermal report for the HP Integrity Superdome/sx2000 server is provided in Table 2-17 on page 74.
Chapter 2
Airflow exit (2600 CFM)
Air flows front to rear (2750 CFM)
System Specifications
Environmental Requirements
ο
C and
73

Hide quick links: