Selecting The Interruption Mode - Omron SYSDRIVE 3G3JV User Manual

Sysdrive 3g3jv series compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

Basic Operation
5-8

Selecting the Interruption Mode

This parameter is used to specify the interruption mode when the STOP command is
input.
The Inverter either decelerates or coasts to a stop according to the interruption mode
selection.
H Selecting the Interruption Mode (n04)
n04
Interruption Mode Selection
Setting
0, 1
range
Set Values
Value
0
Frequency deceleration stop (See notes 1 and 2.)
1
Free running (See note 3.)
Note 1. The Inverter will decelerate to stop according to the setting in n17 for deceleration time 1 if any
of the n36 through n39 parameters for multi-function input is not set to 11 for acceleration/de-
celeration time selection. If any one of the n36 through n39 multi-function input parameters is
set to acceleration/deceleration time selection, the Inverter will decelerate to stop according
to the selected setting of deceleration time when the STOP command is input.
Note 2. If the RUN signal is input again during a deceleration stop, deceleration will be stopped at the
point of the input and acceleration will proceed at that frequency.
Note 3. Do not input a RUN signal during a free-running stop if the motor's rotation speed is not suffi-
cient slowed. If a RUN signal is input under these conditions, a main circuit overvoltage (OV)
or overcurrent (OC) will be detected.
To restart a free-running motor, set a speed search command in one of the multi-function in-
puts 1 to 4 (n36 to n39), use the speed search to detect the speed of the free running motor,
and then accelerate smoothly.
Unit of
1
setting
Description
Chapter 5
Changes during
No
operation
Default setting
0