Data Write/Broadcast Data Write (Function Code: 10 Hex) - Omron SYSDRIVE 3G3JV User Manual

Sysdrive 3g3jv series compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

Communications
D Response
1
2
Function code
3
Number of bytes of attached data
Data in register No. 0020
4
5
6
Data in register No. 0021
7
8
Data in register No. 0022
9
10
Data in register No. 0023
11
12
13
Error
Byte No.
1
2
3
4
CRC-16 check
5

7-4-2 Data Write/Broadcast Data Write (Function Code: 10 Hex)

H Settings and Response
• To write data to the Inverter, such as control I/O and parameter set value data, issue the following DSR
message.
• Consecutive data of a maximum of 16 words (32 bytes for 16 registers) can be written per DSR mes-
sage.
• The register number is allocated to each function item, such as control I/O and parameter functions.
The register number of each parameter is indicated wherever the parameter is explained in this
manual and in Section 10 List of Parameters. For register numbers other than those of parameters,
refer to 7-7 Register Number Allocations in Details.
Note 1. A parameter corresponds to one register (one word), so the "number of registers of write data"
indicates the number of parameters to be written (i.e., the number of consecutive registers
beginning with the first register number).
Note 2. The "number of bytes of attached data" indicates the number of bytes of data written to the
registers attached from that point onwards. The number of registers must equal the number of
bytes divided by two.
g
g
g
g
Data
Chapter 7
02
03
08
MS B
00
LSB
65
00
LSB
00
MSB
00
LSB
00
MSB
01
LSB
F4
AF
82
Data
example
(Hex)
02
83
03
F1
31
7-15

Advertisement

Table of Contents