Torque Compensation Function

This function increases the output torque of the Inverter by detecting an increase in the
motor load.
n63
Torque Compensation Gain
Setting
0.0 to 2.5
range
Set Values
• The default setting does not need any changes in normal operation.
• Change the default setting in the following cases.
The wiring distance between the Inverter and motor is long:
Set the gain to a larger value.
The capacity of the motor is lower than the maximum applicable motor capacity of the Inverter:
Set the gain to a larger value.
The motor vibrates:
Set the gain to a smaller value.
• The torque compensation gain must be adjusted so that the output current at low speed will not exceed
50% of the rated output current of the Inverter, otherwise the Inverter may be damaged.
Unit of
0.1
setting
Chapter 6
Changes during
Yes
operation
Default setting
1.0
6-11