Wiring Control Circuit Terminals - Omron SYSDRIVE 3G3JV User Manual

Sysdrive 3g3jv series compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

Design
Reactor Effects
Harmonics are effectively suppressed when the DC reactor is used with the AC reactor as shown in the
following table.
Harmonics
suppression
i
5th har-
method
monic
No reactor
65
AC reactor
38
DC reactor
30
DC and AC
28
reactors

2-2-5 Wiring Control Circuit Terminals

A control signal line must be 50 m maximum and separated from power lines.
The frequency reference must be input into the Inverter through shielded, twisted-pair
wires.
H Wiring of Control I/O Terminals
Wire each control I/O terminal under the following conditions.
D Wires and Tightening Torque
Multi-function Contact Output (MA, MB, and MC)
Terminal
Tightening
torque N S m
screw size
M3
0.5 to 0.6
Sequential Input (S1 through S5 and SC) and Analog Monitor Output (AM or AC)
Terminal
Tightening
torque N S m
screw size
M2
0.22 to 0.25
Frequency Reference Input (FR, FS, and FC)
Terminal
Tightening
torque N S m
screw size
M2
0.22 to 0.25
2-26
Harmonic generation rate (%)
7th har-
11th har-
monic
monic
41
8.5
14.5
7.4
13
8.4
9.1
7.2
Wire
Wire size
Single wire
0.5 to 1.25
(20 to 16)
Stranded
0.5 to 1.25
wire
(20 to 16)
Wire
Wire size
Single wire
0.5 to 1.25
(20 to 16)
Stranded
0.5 to 0.75
wire
(20 to 18)
Wire
Wire size
Single wire
0.5 to 1.25
(20 to 16)
Stranded
0.5 to 0.75
wire
(20 to 18)
13th har-
17th har-
monic
monic
7.7
4.3
3.4
3.2
5
4.7
4.1
3.2
Recommend
ed wire size
0.75 (18)
Recommend
ed wire size
0.75 (18)
Recommend
ed ire size
0.75 (18)
Chapter 2
19th har-
23rd har-
monic
monic
3.1
2.6
1.9
1.7
3.2
3.0
2.4
1.6
Cable
Cable with polyethylene
sheath
Cable
Cable with polyethylene
sheath
Cable
Special cable with
p y
polyethylene sheath and
y
shield for measurement use
25th har-
monic
1.8
1.3
2.2
1.4

Advertisement

Table of Contents
loading

Table of Contents