Stall Prevention Function

A stall will occur if the motor cannot keep up with the rotating magnetic field on the motor
stator side when a large load is applied to the motor or a sudden acceleration/decelera-
tion is performed.
In the 3G3JV, stall prevention functions can be set independently for accelerating, run-
ning, and decelerating conditions.
n55
Stall Prevention Level during Deceleration
Setting
0, 1
range
Set Values
Value
0
Stall prevention during deceleration
1
No stall prevention during deceleration
• If 1 is set, the motor will be decelerated according to the set deceleration time. If the deceleration time
is too short, the main circuit may result in overvoltage.
• If 0 is set, the deceleration time will be automatically lengthened to prevent overvoltage.
Stall Prevention during Deceleration with n55 Set to 0
Output
frequency
6-6
Unit of
1
setting
Description
Deceleration time is controlled
to prevent overvoltage.
Deceleration time (Set value)
Chapter 6
Changes during
No
operation
Default setting
0
Time