List of Parameters
Parame-
Name
ter No.
(Register
No.
(Hex))
n49
Jump fre-
quency 1
(0131)
n50
Jump fre-
quency 2
(0132)
n51
Jump width
(0133)
n52
DC control
current
(0134)
n53
Interruption
DC control
(0135)
time
n54
Startup DC
control time
(0136)
n55
Stall preven-
tion during
(0137)
deceleration
n56
Stall preven-
tion level dur-
(0138)
ing accelera-
tion
n57
Stall preven-
tion level dur-
(0139)
ing operation
n58
Frequency
detection lev-
(013A)
el
n59
Overtorque
detection
(013B)
function
selection
10-10
Description
Used to set the frequency jump function.
Output
frequency
n51
n51
n50
n49
Note
These values must satisfy the fol-
lowing condition: n49 y n50
Used to impose DC on the induction motor for
braking control.
Set the DC braking current in percentage based
g
on the rated current of the Inverter as 100%.
th
t d
t f th I
Output
frequency
frequency
Minimum
output
frequency
(n14)
n54
Used to select a function to change the deceleration
time of the motor automatically so that there will be
no overvoltage imposed on the motor during decel-
eration.
0: Stall prevention during deceleration enabled
1: Stall prevention during deceleration disabled
Used to select a function to stop the acceleration of
the motor automatically for stall prevention during
acceleration.
Set the level in percentage based on the rated cur-
rent of the Inverter as 100%.
Used to select a function to reduce the output fre-
quency of the Inverter automatically for stall preven-
tion during operation.
Set the level in percentage based on the rated cur-
rent of the Inverter as 100%.
Used to set the frequency to be detected.
Note
The parameter n40 for multi-function output
must be set for the output of frequency detec-
tion levels 1 and 2.
Used to enable or disable overtorque detection and
select the processing method after overtorque
detection.
0: Overtorque detection disabled
1: Overtorque detection only when speed coincides
and operation continues (issues alarm)
2: Overtorque detection only when speed coincides
and output shut off (for protection)
3: Overtorque always detected and operation con-
tinues (issues alarm)
4: Overtorque always detected and output shut off
(for protection)
Setting
range
0.0 to
400
0.0 to
400
Frequency
reference
reference
0.0 to
25.5
0 to
100
p
g
t
100%
0.0 to
25.5
0.0 to
25.5
Time
n53
0, 1
30 to
200
30 to
200
0.0 to
400
0 to 4
Chapter 10
Unit of
Default
Changes
setting
setting
during
operation
0.1 Hz
0.0
No
(see
note 1)
0.1 Hz
0.0
No
(see
note 1)
0.1 Hz
0.0
No
1%
50
No
0.1 s
0.5
No
0.1 s
0.0
No
1
0
No
1%
170
No
1%
160
No
0.1 Hz
0.0
No
1
0
No
Refer-
ence
page
6-16
6-16
6-16
6-5
6-5
6-5
6-6
6-7
6-8
6-18
6-9