List of Parameters
Parame-
Name
ter No.
(Register
No.
(Hex))
n60
Overtorque
detection lev-
(013C)
el
n61
Overtorque
detection time
(013D)
n62
UP/DOWN
command fre-
(013E)
quency
memory
n63
Torque com-
pensation
(013F)
gain
n64
Motor rated
slip
(0140)
n65
Motor no-load
current
(0141)
n66
Slip com-
pensation
(0142)
gain
n67
Slip com-
pensation
(0143)
time constant
n68
RS-422A/485
communica-
(0144)
tions time-
(See note
over detec-
3.)
tion selection
Description
Used to set overtorque detection level.
Set the level in percentage based on the rated cur-
rent of the Inverter as 100%.
Used to set the detection time of overtorque.
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to store the adjusted frequency reference with
the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or more.
Used to set the gain of the torque compensation
function.
The default setting does not need any changes in
normal operation.
Used to set the rated slip value of the motor in use.
Note
Used as the constant of the slip compensation
function.
Used to set the no-load current of the motor in use
based on the rated motor current as 100%.
Note
Used as the constant of the slip compensation
function.
Used to set the gain of the slip compensation func-
tion.
Note
The slip compensation function is disabled
with n66 set to 0.0.
Used for the response speed of the slip compensa-
tion function.
Note
The default setting does not need any
changes in normal operation.
Used to set whether a communications time-over
(CE) is detected if there is an interval of more than 2
s, and to select the method of processing the
detected communications time-over.
0: Detects a time-over and fatal error and coasts to
a stop.
1: Detects a time-over and fatal error and deceler-
ates to a stop in deceleration time 1.
2: Detects a time-over and fatal error and deceler-
ates to a stop in deceleration time 2.
3: Detects a time-over and nonfatal error warning
and continues operating.
4: No time-over is detected.
Setting
Unit of
Default
range
setting
setting
30 to
1%
160
200
0.1 to
0.1 s
0.1
10.0
0, 1
1
0
0.0 to
0.1
1.0
2.5
0.0 to
0.1 Hz
Varies
20.0
with the
capac-
ity.
0 to 99
1%
Varies
with the
capac-
ity.
0.0 to
0.1
0.0
2.5
0.0 to
0.1 s
2.0
25.5
0 to 4
1
0
Chapter 10
Changes
Refer-
during
ence
operation
page
No
6-9
No
6-10
No
6-19
Yes
6-11
Yes
6-12
No
6-12
Yes
6-12
No
6-12
No
7-5
10-11