Advanced Operation
This chapter provides information on the use of advanced functions of the Inverter for
operation.
Refer to this chapter to use the various advanced functions, such as stall prevention,
carrier frequency setting, overtorque detection, torque compensation, and slip com-
pensation.
6-1

Setting the Carrier Frequency

The carrier frequency of the 3G3JV can be fixed or varied in proportion to the output fre-
quency.
n46
Carrier Frequency Selection
Setting
1 to 4, 7 to 9
range
Note The default setting varies with the capacity of the Inverter model.
Set Values
Value
1
2.5 kHz
2
5.0 kHz
3
7.5 kHz
4
10.0 kHz
7
2.5 kHz (12×): 12 times as high as output frequency (between 1.0 and 2.5 kHz)
8
2.5 kHz (24×): 24 times as high as output frequency (between 1.0 and 2.5 kHz)
9
2.5 kHz (36×): 36 times as high as output frequency (between 1.0 and 2.5 kHz)
• The default setting does not need any changes in normal operation.
• Change the default setting in the following cases.
The wiring distance between the Inverter and motor is long:
Set the Inverter to a lower carrier frequency.
Reference carrier frequency: 10 kHz at a maximum wiring distance of 100 m and 5 kHz at a
Excessive speed or torque dispersion at low speed:
Set the carrier frequency to a lower value.
6-2
Unit of
1
setting
Description
wiring distance exceeding 100 m.
Chapter 6
Changes during
No
operation
Default setting
(see note)