Main Circuit Terminals; Control Circuit Terminals - Omron SYSDRIVE 3G3JV User Manual

Sysdrive 3g3jv series compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

Design
H Main Circuit Terminals
Symbol
R/L1
Power supply input
terminals
terminals
S/L2
T/L3
Motor output terminals
U/T1
V/T2
W/T3
Connection terminals +1
+1
and +2:
DC reactor connection
DC reactor connection
+2
terminals
+1 and –:
+1 and –:
DC power supply input
terminals
Ground terminal
Note The maximum output voltage corresponds to the power supply input voltage of the Inverter.
H Control Circuit Terminals
Symbol
Input
S1
Forward/Stop
S2
Multi-function input 1
(S2)
S3
Multi-function input 2
(S3)
S4
Multi-function input 3
(S4)
S5
Multi-function input 4
(S5)
SC
Sequence input com-
mon
FS
Frequency reference
power supply
FR
Frequency reference in-
put
FC
Frequency reference
common
Name
3G3JV-A2j: 3-phase 200 to 230 V AC
3G3JV-ABj: Single-phase 200 to 240 V AC
3G3JV ABj Si
3G3JV-A4j: 3-phase 380 to 460 V AC
3G3JV-A4j: 3-phase 380 to 460 V AC
Note
3-phase power supply output for driving motors.
3G3JV-A2j: 3-phase 200 to 230 V AC
3G3JV-ABj: 3-phase 200 to 240 V AC
3G3JV-ABj: 3-phase 200 to 240 V AC
3G3JV-A4j: 3-phase 380 to 460 V AC
Connect the DC reactor for suppressing harmonics to terminals +1
and +2.
When driving the Inverter with DC power, input the DC power to
terminals +1 and –.
(Terminal +1 is a positive terminal.)
(Terminal +1 is a positive terminal )
Be sure to ground the terminal under the following conditions.
3G3JV-A2j: Ground at a resistance of 100 Ω or less.
3G3JV-ABj: Ground at a resistance of 100 Ω or less.
3G3JV-A4j: Ground at a resistance of 10 Ω or less, and connect
to the power supply's neutral phase to conform to EC Directives.
Note
Name
Description
l
h
200 t 240 V AC
Connect single-phase input to terminals R/L1 and S/L2.
Be sure to connect the ground terminal directly to the
motor frame ground.
Function
Forward at ON. Stops at
OFF.
Set by parameter n36
(Reverse/Stop)
Set by parameter n37
(Fault reset)
Set by parameter n38
(External fault: Normally
open)
Set by parameter n39
(Multi-step reference 1)
Common for S1 through
S5
DC power supply for fre-
quency reference use
Input terminal for fre-
quency reference use
Common for frequency
reference use
Chapter 2
Signal level
Photocoupler
8 mA at 24 V DC
Note
NPN is the default setting
for these terminals. Wire
th
them by providing a
b
idi
common ground. No
external power supply is
external power supply is
required. To provide an
external power supply and
wire the terminals through
a common positive line,
however, set the SW7 to
PNP and make sure that
PNP and make sure that
the power supply is at
24 V DC ±10%.
20 mA at 12 V DC
0 to 10 V DC
(input impedance: 20 kΩ)
( p
p
0
g
i i
li
)
2-11