Selecting V/f pattern

Adjusting torque according to application
Adjust motor torque by using "V/f pattern" and "full-range automatic torque
boost".
• V/f pattern setting
Set V/f pattern by n09 to n15 as described below. Set each pattern when
using a special motor (high-speed motor, etc.) or when requiring special
torque adjustment of machine.
V: (VOLTAGE)
n10
n13
n15
0
n14 n12 n11
Constants
Name
No.
n09
Max. output frequency
n10
Max. voltage
Max. voltage output
n11
frequency (base frequency)
n12
Mid. output frequency
Mid. output
n13
frequency voltage
n14
Min. output frequency
Min. output
n15
frequency voltage
* For 400-volt class inverters
f
n09
(FREQUENCY)
Unit
0.1Hz
1V
0.1Hz
0.1Hz
1V
0.1Hz
1V
Be sure to satisfy the following
conditions for the setting of n09 to
n15.
n14 Ã n12 < n11 Ã n09
If n14 = n12 is set, the set value of n13
is disabled.
Setting range
50.0 to 400.0Hz
1 to 255V
(1 to 510V)
0.2 to 400.0Hz
1 to 399Hz
1 to 255V
(1 to 510V)*
0.1 to 10.0Hz
1 to 50V
(1 to 100V)*
Initial
Setting
50.0Hz
200V
*
(400V)
50.0Hz
1.3Hz
12V
(24V)
1.3Hz
12V
(24V)