Advanced Operation
H Frequency Detection
• The parameter n40 for multi-function output must be set for frequency detection output.
Set value: 2 for frequency detection
Frequency Detection Operation
Output
frequency
Frequency
detection
H Frequency Detection Levels 1 and 2
• The parameter n40 for multi-function output must be set for frequency detection output.
Set value: 4 for frequency detection level 1 (Output frequency y n58)
Set value: 5 for frequency detection level 2 (Output frequency x n58)
• Set the frequency detection level in n58.
n58
Frequency Detection Level
Setting
0.0 to 400 (Hz)
range
6-18
Detection width ±2 Hz
Unit of
setting
Reset width ±4 Hz
Frequency reference
Changes during
operation
0.1 Hz
Default setting
(see note)
Chapter 6
Time
Time
No
0.0