Specifications
9-2-11 AC Reactor
H 3G3IV-PUZBABj (Yaskawa Electric)
The AC Reactor suppresses harmonic current generated from the Inverter and improves the power fac-
tor of the Inverter. Connect the AC Reactor to the Inverter if the capacity of the power supply is much
larger than that of the Inverter. Select the AC Reactor model from the following table according to the
motor capacity.
H Connection Example
H Applicable Range
H Applicable Models and Dimensions
D 200-V Class
Max. applicable
motor capacity (kW)
0.1 to 0.2
0.4
0.75
1.5
2.2
3.7
9-16
MCCB AC Reactor
Power supply
capacity (kVA)
Model
Current (A)
3G3IV-
PUZBABj
2A7.0MH
2
2.5A4.2MH
2.5
5A2.1MH
5
10A1.1MH
10
15A0.71MH
15
20A0.53MH
20
Motor
AC Reactor required
for smooth operation
under present power
supply conditions
AC Reactor
not required
Inverter capacity (kVA)
Inductance
(mH)
7.0
4.2
2.1
1.1
0.71
0.53
Chapter 9
Loss (W)
Weight (kg)
8
2.5
15
2.5
15
2.5
25
3
30
3
35
3