NAV IP Access controller
or  multiple alarm  outputs. Alarm  components,  configuration  basics,  and  menu  settings  are  introduced 
below. 
 
5.9.1 Components for Alarm 
NAV  Controller  consists  of  two  basic  components:  one  main  module  and  one  door  module.  Users  can 
additionally install three more door modules and one alarm module.
These three types of modules are all equipped with alarm function. The main module has 2 alarm inputs 
and 2 alarm outputs, called Main Alarm Output and Auxiliary Alarm Output respectively.
Each door module has 2 alarm outputs, which usually react to alarm events on the corresponding door. 
However, it can be set to react to other alarm events as well. Alarm outputs on the door module can 
connect up to 5A external alarm devices. 
The alarm module has 8 alarm inputs and 8 alarm outputs. 8 alarm inputs can connect to external alarm 
input  devices,  such  as  PIR  motion  sensor,  glass  sensor  and  etc.  8  alarm  outputs  can  connect  up  to  2A 
external alarm devices. 
The above mentioned are physical devices providing alarm functions 
User  can  freely  define  the  allocation  of  any  input  to  any  output.  The  following  section  outlines  basic 
concepts for events, alarm and configuration. 
5.9.2 Alarm Configuration Basics 
NAV Controller keeps track of all events in the access control system, either legal or illegal, either normal 
or abnormal.  For example, access granted, access denied and so on.  
Some events are critical which must trigger the alarm output, like the firm alarm input, the zone alarm 
input and etc. But some events are not that important to trigger the alarm output, like the denied access 
due to the invalid time. These settings all depend on the users' requirements. NAV Controller collects all 
events that might trigger the alarm output and provides the full capacity to enable or disable the alarm 
output on these events. 
Sometimes  user  wants  to  allocate  a  particular  event  to  a  particular  alarm  output,  or  allocate  alarm 
inputs in certain area to multiple alarm outputs. NAV Controller delivers all the function and flexibility 
user need. User can define whether certain event will trigger an alarm, and can further specify to which 
alarm output that event is allocated. 
All events that might trigger an alarm are listed below: 
Alarm input 0~9, unknown card, expired card, invalid card, invalid door, invalid time, card anti‐pass back 
fail, card PIN fail, SYS PIN fail, ARM PIN fail, door forced open, door held open, reader lost, and remote 
alarm. 
All these events can be allocated to any alarm relay output on main module, door module, and alarm 
module. The detailed configuration method is introduced in the following section. 
 
5.9.3 Enter Alarm Setting Menu 
Under System menu, press 
four times to bring up the following window:
 