5.1

Installation requirements

Recommended protective devices and cable cross-sections
1. Recommended upstream protection
9PX 6K SP
utility
G
N
L2
2. Recommended cable cross-sections
Terminal
position
L1
L2
N
Copper wire, solid or stranded.
9PX-6K-SP_EN
UPS power rating
6000VA
3 pole circuit breaker
L1
Wire
Terminal wire
function
size rating
Phase
8-5 AWG (10-16 mm
Phase
Neutral
Ground

5. Power cable connection

Upstream circuit breaker
30A
L1
to UPS Input AC source
L2
N
Minimum input
wire size
)
8 AWG (194°F)
2
10 mm² (90°C)
Tightening
torque
18 lb in / 2.03 Nm