Hardwire Connection of Output Power Cable to UPS

w This type of connection must be carried out by qualified electrical personnel.
w Before carrying out any connection, check that the battery circuit breaker and the upstream protection device
(Normal AC source) is open «0» (off).
Output Terminal
GND
L2(N)
2
1
2
2 & 3
L1
2
4
1. Remove the top of the terminal box cover
(2 screws) with the included screwdriver.
2. Insert the output cable/conduit (provided by
others) through the cable knockout (2).
3. Connect the outlet cable to the output terminal
block.
4. Tighten the cable/conduit flange and refit the
terminal box cover by means of the 2 screws.
Always connect the ground wire first.
3
Note: 10' Input cable with L6-30P (3) comes
attached by EATON. Output cable/conduit (2) is not
included (provided by others).
3
3