Bulletin 1609 UPS
Battery Wiring and
Installation (cont.)

Mount the UPS

8
4. Fold the battery container and seal it with tape.
5. To connect the batteries to the UPS, insert the batteries into the battery
compartment, open the white connector retainer and connect the two
cables together as shown in the photo below.
6. To complete the battery installation, close the white connector
retainer and reattach the battery door with the three screws
(torque of 8.7+/-1.7 lb-in).
The UPS-D is designed to mount on the back of the panel or to the floor of the
enclosure. The UPS mounts to a bracket assembly (1609-BRK) that allows it
to mount to either the panel or floor (see Figure 1 below).
Figure 1 - Mounting the UPS
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013