Bul. 1609-B Specifications - Allen-Bradley Bulletin 1609 User Manual

Bulletin 1609 uninterruptible power supply
Hide thumbs Also See for Bulletin 1609:
Table of Contents

Advertisement

Bulletin 1609 UPS

Bul. 1609-B Specifications

Input
V nom.
Capacity
Voltage Range, default
Voltage Range, widest online
Current nom.
Capacity Frequency
PFC
Output
V nom.
Capacity
Online
Output Voltage Range, default
Output Voltage Range, widest online
Transfer Point Accuracy
On Battery
V nom
Frequency
THD
Short Circuit Protection
Crest Factor
Efficiency
On Battery (Typical with resistive load)
Online - Typical with resistive load excluding AVR mode) 94% Typical with resistive load
Protection
Surge
Overload (Shutdown after 10 s)
Overload (Shutdown immediately)
Output Short: Online
Output Short: Battery
Thermal Protection
Regulatory
Safety
EMC
Markings
Battery Pack
Run Time
Type
Voltage
Charger
Recharger Time
Lifetime
Environment
Temperature
Altitude
Humidity
Heat Output
Audible Noise
Mechanical
Approximate Dimensions L*W*H In. (mm)
Approximate Weight lbs (kg)
28
1609-B600N
120V
600 VA (360 W)
96...138V
96...138V
5.4 A
50/60 Hz ± 3 Hz
None
120V
600 VA (360 W)
96...138V
96...138V
± 3%
120V (step wave)
50/60 Hz ± 1 Hz
47.5% (step wave)
2.5:1
80% Typical with resistive load
380 Joules (Total performance rated with 10*1000 μ s pulse)
> 110...130% - shutdown after 5 sec
130% shutdown immediately
Premises branch circuit over-current protection
Shutdown
UPS inside temperature ≥ 70 °C
UL1778, CSA C22.2 No. 107.3-05, EN/IEC62040-1
FCC & CE (Class A)
UL, cULus, FCC, CE, C-Tick
≥5 min (at 25 °C, full load = 360W, PF = 0.6...0.75)
Sealed Lead Acid Battery
12V/5Ah (for 0...40 °C: B.B. BP5...12)
12V/5.5 Ah (for 0...50 °C: B.B. HRL5.5...12)
24V
Current limited, constant voltage float charger
Less than 12 hrs to 90% capacity after discharge with full load
2...3 years at 25 °C ambient temperature
Operating Standard Battery 0...+40 °C (+32...+104 °F) Hi-Temperature Battery 0...+50 °C (+32...+122 °F)
Non-operating/Storage -15...+45 °C (+5...+113 °F)
Operating 0...6600 feet (0... 2000 meters)
Operating/Storage 5...95% RH (Non-condensing)
On Line, Full load: 107 BTU/hr
On Line, Full load, Charging: 160 BTU per hour
On Battery: Full Load: 1228 BTU per hour
< 45 dBA @ Front Side 1 Meter
6.1 x 11 x 7.09 (155 x 300 x 180)
14.5 (6.6)
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
1609-B1000N
120V
1000 VA (600 W)
8.9 A
50/60 Hz ± 3 Hz
None
1000 VA (600 W)
47.6% (step wave)
≥2 min (at 25 °C, full load = 600W, PF = 0.6...0.75)
On Line, Full load: 178 BTU/hr
On Line, Full load, Charging: 231 BTU per hour
On Battery: Full Load: 2047 BTU per hour
14.7 (6.7)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

1609-d1609-b