Allen-Bradley 1609-P3000N User Manual
Allen-Bradley 1609-P3000N User Manual

Allen-Bradley 1609-P3000N User Manual

3000/5000 va ups; tower/rack-mount 3u uninterruptible power supply
Hide thumbs Also See for 1609-P3000N:

Advertisement

Allen-Bradley
User Manual for 3000/5000 VA UPS
1609-P3000N
1609-P3000H
1609-P3000A
1609-P5000E
Uninterruptible Power Supply
41063-260-01(1)
3000 VA 120 VAC
3000 VA 208 VAC
3000 VA 230 VAC
5000 VA 208/230 VAC
Tower/Rack-Mount 3U
990-2671 09/2005

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 1609-P3000N

  • Page 1 Allen-Bradley User Manual for 3000/5000 VA UPS 1609-P3000N 3000 VA 120 VAC 1609-P3000H 3000 VA 208 VAC 1609-P3000A 3000 VA 230 VAC 1609-P5000E 5000 VA 208/230 VAC Tower/Rack-Mount 3U Uninterruptible Power Supply 41063-260-01(1) 990-2671 09/2005...
  • Page 2: Installation

    NSTALLATION Read the Safety Instruction sheet before installing the UPS. Unpacking Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage. The packaging is recyclable; save it for reuse or dispose of it properly. Check the package contents: Front bezel Literature kit containing: ®...
  • Page 3 USING POWER CORD NITS 1609-P3000N – Use captive 8 ft cord. NEMA L5-30 Plug is attached to this cord. 1609-P3000H – Use in captive 8 ft cord. NEMA L6-30 Plug is attached to this cord. 1609-P3000A – User must supply power cord. Power cord must mate with IEC 320 C20 inlet.
  • Page 4 Connecting the Battery modules and Attaching the Front Bezel ∂ • ÷ ≠...
  • Page 5 ASIC ONNECTORS Power management software and interface cable can be used with the UPS. Use only a supplied or approved interface cable. serial com Any other serial interface cable will be incompatible with the UPS connector. Manual bypass enables the user to manually put connected equipment into bypass mode.
  • Page 6: Circuit Breakers

    IRCUIT REAKERS output circuit breakers 1609-P5000E 1609-P3000A output circuit breakers 1609-P3000N output circuit breaker 1609-P3000H...
  • Page 7: Connecting Equipment And Power To The Ups

    Connecting Equipment and Power to the UPS Connect equipment to the UPS. Avoid using extension cords. Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all connected equipment is switched ON. The equipment will not be powered until the UPS is turned on.
  • Page 8: Operation

    PERATION RONT ISPLAY Load Battery Charge Indicator Description The Online LED illuminates when the UPS is drawing utility power and performing Online double conversion to supply power to connected equipment. The UPS is supplying battery power to the connected equipment. On Battery The Bypass LED illuminates indicating that the UPS is in bypass mode.
  • Page 9: On Battery Operation

    Feature Function Cold Start When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment. The UPS will emit two beeps. During the second beep, release the button. Self-Test Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default).
  • Page 10 ONFIGURABLE TEMS ETTINGS ARE MADE THROUGH SUPPLIED OWER HUTE SOFTWARE OPTIONAL ETWORK ANAGEMENT CARDS ERMINAL ACTORY ELEC TABLE UNCTION ESCRIPTION EFAULT HOICES Automatic Self-Test Every 14 days Every 7 days(168 hours), Set the interval at which the (336 hours) 14 days (336 hours) UPS will execute a self-test.
  • Page 11 The output power can be disabled in an emergency by closing a switch connected to the EPO. Adhere to National and local electrical codes when wiring the EPO. Rockwell Automation recommends Allen-Bradley Catalog Number 800F Emergency Stop Operator as the interface to the EPO to connector.
  • Page 12 Use one of the following cable types to connect the UPS to the EPO switch: • CL2: Class 2 cable for general use • CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air. • CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
  • Page 13: Maintenance , And Transport

    AINTENANCE RANSPORT Replacing the Battery Module This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipment on during the procedure. The battery replacement procedure must include replacing all battery modules in the UPS and connected external battery pack(s).
  • Page 14 EPLACING ATTERY MODULES  Disconnecting the Battery for Transport Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery(s) may remain in the UPS. Shut down and disconnect any equipment attached to the UPS. Shut down and disconnect the UPS from the power supply.
  • Page 15: Troubleshooting

    ROUBLESHOOTING ROBLEM AND OSSIBLE OLUTION AUSE WILL NOT TURN ON Battery not connected pro perly. Check that the battery connectors are fully engaged. button not pushed. Press the button once to power the UPS and the connected equipment. UPS not connected to utility Check that the power cable from the UPS to the utility power supply is securely power supply.
  • Page 16: Online Led

    ROBLEM AND OSSIBLE OLUTION AUSE BYPASS ILLUMINATES The bypass switch has been If bypass is the chosen mode of operation, ignore the illuminated LED. turned on manually or through If bypass is not the chosen mode of operation move the bypass switch on the an accessory.
  • Page 17: Contact Information

    Service If the UPS requires service do not return it to the dealer. Follow these steps: Review the problems discussed in the Troubleshooting section of this manual to eliminate common problems. If the problem persists, contact Rockwell Automation Customer Support. Refer to Contact Information below.
  • Page 18: Safety Information

    Safety Information - SAVE THIS GUIDE This Safety Guide contains important instructions that should be followed during installation and maintenance of the equipment and batteries. It is intended for customers who setup, install, relocate, or maintain equipment. Changes and modifications to this unit not expressly approved could void the warranty. Handling Safety <18 kg (<40 lb) 32–55 kg (70–120 lb)