Ups Management Software Troubleshooting - Allen-Bradley Bulletin 1609 User Manual

Bulletin 1609 uninterruptible power supply
Hide thumbs Also See for Bulletin 1609:
Table of Contents

Advertisement

Bulletin 1609 UPS
Management Software
Troubleshooting
Status Indications
Indication Description
Buzzer Alarm
The UPS has detected a fault and generate a buzzer
alarm.
Test In Progress
The UPS is currently in a test mode.
UPS Fault
The UPS has detected a fault and disabled its output.
Battery Low
The UPS has detected that the batteries are low.
Power Failed
The UPS has detected that the input utility voltage
has failed.
Overheat
The ambient temperature is greater than 60 °C, or
some internal components are over temperature.
Overload
The UPS has detected that output load of UPS is
greater than 110%.
Load Warning
The output load over the warning threshold.
Load Severity
The output load over the severity threshold.
UPS Disconnect
The UPS has detected a communication loss between
the UPS and the computer.
Output Abnormal
To indicate the output voltage is abnormal.
Output Off
The UPS is operating in standby mode, or UPS is
faulted.
UPS System Off
The UPS system is in the standby state.
Awaiting Power
The battery is depleted and the UPS awaits the return
of input utility voltage.
Battery Need Replace
The UPS has detected that the battery is bad or
opened.
Battery Depleted
The UPS has detected that the batteries are depleted.
General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately
to turn the UPS off then press and hold the button again until one beep is heard
then release to enable the output.
Solution
Verify the type of fault from the Status Indicators or the LEDs on the UPS for further
troubleshooting.
Do not interrupt the UPS testing. The UPS is doing battery test.
Verify the type of fault from the Status Indicators or the LEDs on the UPS for further
troubleshooting.
To clear fault, follow the General Clear Fault Procedure described above and if the fault persists,
contact Technical Support.
The batteries must be charged for 24 hours and re-verify the battery status. If the batteries still
indicate to be low, replace the batteries.
Verify that the input utility voltage is within the UPS's input specification.
If it is not, make the necessary correction to the input utility power system.
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed
40 °C(1609-SBAT) or 50 °C (1609-HBAT). If the temperature exceeds the UPS rating, make the
necessary correction to the system. This issue may be corrected by improving the room ambient
temperature (add ventilation or provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above and if the fault persists,
contact Technical Support.
Verify that the load does not exceed the load specification. If it is, remove the excess load from the
UPS's output and clear its fault. If the problem persists, have a qualified electrician troubleshoot
the UPS Load System and make the necessary corrections or select the appropriate size of UPS. If
the problem persists, contact Technical Support.
Verify the output load. If it is close to 100% load, remove the excess load or select the appropriate
size of UPS.
Verify the output load. If it is actually at 100% load, remove some of the non-essential load or
select the appropriate size of UPS.
Please check the USB cable between computer and UPS for secure connection or replace the cable
with a known good cable.
If communication is established, re-open the UPS Management software. If the problem persists,
contact Technical Support.
Have qualified electrician verify that the quality of the output voltage and the input utility voltage
are within its specification.
To clear fault, follow the General Clear Fault Procedure described above and if the problem
persists, contact Technical Support.
If it is identified as the UPS fault shutdown then turn the UPS off, and then turn UPS on again to
reset the fault. If the fault persists, contact Technical Support.
If it is identified as the UPS fault shutdown then turn the UPS off. Turn UPS on again to reset the
fault. If the fault persists, contact Technical Support.
Apply the input utility voltage to the UPS.
Have a qualified electrician verify the battery connection for good contact and charge the
batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
indicates Battery Need Replace, new batteries are required.
Have a qualified electrician verify the battery connection for good contact and charge the
batteries for 24 hours.
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
indicates Battery Depleted, new batteries are required.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013