Ups Led Fault Indicators; Output Short Circuit; Output Overload; Over Temperature From The Heatsink - Allen-Bradley Bulletin 1609 User Manual

Bulletin 1609 uninterruptible power supply
Hide thumbs Also See for Bulletin 1609:
Table of Contents

Advertisement

UPS LED Fault Indicators

No.
Fault
1

Output Short Circuit

GRN
RED
2

Output Overload

RED
GRN
3
Over Temperature from the
Heatsink
RED
GRN
4

Over Ambient Temperature

RED
GRN
5
Over Voltage from The DC/DC
Converter of Inverter
RED
GRN
6

Over Voltage from The Inverter

GRN
RED
7

Under Voltage from The Inverter

RED
GRN
General Clear Fault Procedure
Press and hold the button until three beeps are heard then release immediately
to turn the UPS off then press and hold the button again until one beep is
heard then release to enable the output.
Description
Solution
The UPS has detected a
Have a qualified electrician troubleshoot the load connected to the output to the UPS and remove the
short circuit on the Output
short circuit if present.
of the UPS and disabled its
output.
The UPS has detected an
To clear fault, follow the General Clear Fault Procedure described above. If the problem persists, contact
overload and disabled its
Technical Support.
output.
Verify the load connected to the output of the UPS. Ensure that the load does not exceed the output
rating of the UPS. If the load exceeds the rating of the UPS please remove excess load or select the
appropriate size UPS. If the problem persists, contact Technical Support.
To clear fault, follow the General Clear Fault Procedure described above.
The UPS has detected an
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
over temperature of the
(1609-SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the
heatsink and disabled its
system. This issue may be corrected by improving the room ambient temperature (add ventilation or
output.
provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
The UPS has detected an
Have a qualified electrician checked the ambient temperature to make sure that it does not exceed 40 °C
over ambient temperature
(1609SBAT) or 50 °C (1609-HBAT). If it is over temperature, make the necessary correction to the
and disabled its output.
system. This issue may be corrected by improving the room ambient temperature (add ventilation or
provide air conditioning).
To clear fault, follow the General Clear Fault Procedure described above.
The UPS has detected an
Have a qualified electrician verify that the quality of utility voltage is within specification.
over voltage of the DC/DC
To clear the fault, follow the General Clear Fault Procedure described above.
Converter and disabled its
If the fault is still present after attempting to clear fault, contact Technical Support.
output.
The UPS has detected high
Have a qualified electrician verify that the quality of utility voltage is within specification.
voltage on the inverter
To clear fault, follow the General Clear Fault Procedure described above.
and disabled its output.
If the fault is still present after attempting to clear fault, contact Technical Support.
The UPS has detected low
Have a qualified electrician verify that the quality of utility voltage is within specification.
voltage on the inverter
To clear fault, follow the General Clear Fault Procedure described above.
and disabled its output.
If the fault is still present after attempting to clear fault, contact Technical Support.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS
23