Mount the UPS

Hardwire UPS

Selection of Cables

The 1609-B UPS products are designed to mount to a heavy duty DIN-rail
(see Figure 3 below). The 1609-B UPS products are also designed with an
optional bracket assembly (Cat 1609-BRK) that allows it to mount to either
the panel or floor (see Figure 4 below).
Figure 3 - Standard DIN-Rail Mount
Figure 4 - Optional Panel or Floor Mount
Wiring of the UPS should be performed by a qualified electrician using the
appropriate wire gauges.
Table 3 - AC Main Input / Output Wiring for UPS
Item
Specification
Wire Size
14 AWG
Minimum Temperature
75 °C
Wire Conductor Material
Copper only
Tightening Torque for Terminals
4.4 lb - in.
WARNING: To reduce the risk of fire, connect only to a circuit with 20 amperes
maximum branch circuit overcurrent protection in accordance with the National
Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit.
To reduce the risk of fire, connect only to a circuit with branch circuit overcurrent
protection for 20 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Bulletin 1609 UPS