Over Voltage From The Output; Under Voltage From The Output; Fan Failure; Charger Failure - Allen-Bradley Bulletin 1609 User Manual

Bulletin 1609 uninterruptible power supply
Hide thumbs Also See for Bulletin 1609:
Table of Contents

Advertisement

Bulletin 1609 UPS
No.
Fault
8

Over Voltage from The Output

of AVR
BLINK
GRN
RED
9

Under Voltage from The Output

of AVR
RED
BLINK
GRN
10

Fan Failure

RED
GRN
11

Charger Failure

GRN
BLINK
GRN
12

TMOV Failure

GRN
BLINK
GRN
13

Missing Battery

BLINK
GRN
RED
14

Replace Batteries

GRN
RED
24
Description
Solution
The UPS has detected an
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
over voltage on the output
within its specification.
of AVR and disabled its
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists,
output.
contact Technical Support.
The UPS has detected low
Have qualified electrician verify that the quality of the output voltage and the input utility voltage are
voltage on the output of
within its specification.
AVR and disabled its
To clear fault, follow the General Clear Fault Procedure described above and if the problem persists,
output.
contact Technical Support.
The UPS has detected that
To clear fault, follow the General Clear Fault Procedure described above and if the Fan Failure persists,
the fan of the UPS has
contact Technical Support.
failed and disabled its
output.
The UPS has detected that
Clear this fault by removing the input utility voltage and batteries then plug the batteries back in place
the battery charger circuit
and turn the input utility voltage back on. Enable the UPS output to verify the fault.
has failed; however, the
If the Charger Failure persists, contact Technical Support.
UPS will continue running.
The UPS has detected that
Schedule to have a qualified electrician replace the MOV board (1609-SPD).
the MOV circuit has failed;
Remove the input utility power before service on this 1609-SPD due to risk of electrical shock.
however, the UPS will
continue enabling the
output.
The UPS has detected that
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
the batteries are missing;
24 hours.
however, the UPS will
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
continue enabling the
indicates Missing Battery, new batteries are required.
output.
The UPS has detected that
Have a qualified electrician verify the battery connection for good contact and charge the batteries for
the batteries are bad;
24 hours.
however, the UPS will
To clear fault, follow the General Clear Fault Procedure described above. If the battery status still
continue running.
indicates Replace Battery, new batteries are required.
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013