Selection Of Cables; Connect The 1609-Exbat To The Ups - Allen-Bradley Bulletin 1609 User Manual

Bulletin 1609 uninterruptible power supply
Hide thumbs Also See for Bulletin 1609:
Table of Contents

Advertisement

Bulletin 1609 UPS

Selection of Cables

Connect 1609-EXBAT
to the UPS
18
Table 4 - DC Input/Output Wiring for External Battery Cabinet
Item
Wire Size
Minimum temperature
Wire conductor material
Tightening torque for terminals
To install the 1609-EXBAT unit with the 1609-D UPS, connect the three 10
AWG wires from the 1609-EXBAT terminals to the 1609-D UPS terminals
marked as 'EXTERNAL BATT PACK (36V)'. (See Figure 8)
Dispose of used batteries according to the battery instructions.
Figure 8 - System Wiring
Rockwell Automation Publication 1609-UM009A-EN-P - January 2013
Specification
10 AWG
75 °C
Copper only
12 lb-in.