Installation Instructions

Electrical connection

All electrical work must be performed by a
qualified service technician in accordance
with applicable codes and standards.
The connecting terminal is located behind a
cover.
The machine must only be connected to the
voltage and frequency shown on the data
plate.
The machine is equipped with a multi-tap
transformer.
Steam heated washers are factory set to
3 phase, 208 V, 60 Hz
They can be converted to
3 phase, 240 V, 60 Hz by a Miele Service
Technician.
Electrically heated washers are factory set
to 3 phase, 230 V, 50/60 Hz
They can be converted to
3 phase, 208 V, 60 Hz by a Miele Service
Technician.
To activate the heating the water level in the
drum must be 2" (50 mm) high.
A motor overload protection is located in the
motor winding.
See the enclosed wiring and installation
diagrams.
42
Steam connection
The steam connection must only be
connected by a certified installer. For more
information see the enclosed installation
plan and the installation manual.
Connecting the dispensing pumps
The connecting terminal for 4 time controlled
dispensing pumps is located behind the
cover next to the electrical connection.
The dispensing pumps can be operated
without the multifunction module.