I/O And Data Area Allocations; I/O Allocations - Omron SRM1(-V2) Operation Manual

Compobus/s controller
Hide thumbs Also See for SRM1(-V2):
Table of Contents

Advertisement

I/O and Data Area Allocations

1-4
I/O and Data Area Allocations

1-4-1 I/O Allocations

8
The input bits of SRM1 words 000 to 007, and the output bits of words 010 to 017,
are allocated to the CompoBus/S Slave. These allocations are shown in the fol-
lowing table.
I/O
Word address
Inputs
Outputs
IN0 to IN15 are Input Slave node numbers, and OUT0 to OUT15 are Output
Slave node numbers.
If the maximum number of CompoBus/S devices is set to 16, then IN8 to IN15
and OUT8 to OUT15 can be used as work bits.
Words IR 008, IR 009, IR 018, and IR 019 can be used as work words.
The bits for two node number are allocated to 16-point Slaves so that all bits are
in the same word. If an even node address is set, the node address that is set
and the next node address following it will be used. For example, if node address
6 is set for a 16-point Output Slave, bits for node addresses OUT6 and OUT7 will
be used. If an odd node address is set, the node address that is set and the pre-
vious node address will be used. For example, if node address 3 is set for a
16-point Output Slave, bits for node addresses OUT2 and OUT3 will be used.
All of the bits for one node address are allocated to a 4-point Slave. If an even
numbered node address is set, bits 00 to 03 are used and bits 04 to 07 are not
used. If an odd numbered node address is set, bits 8 to 11 are used and bits 12 to
15 are not used.
15 to 08
000
IN1
001
IN3
002
IN5
003
IN7
004
IN9
005
IN11
006
IN13
007
IN15
010
OUT1
011
OUT3
012
OUT5
013
OUT7
014
OUT9
015
OUT11
016
OUT13
017
OUT15
Section
1-4
Bits
07 to 00
IN0
IN2
IN4
IN6
IN8
IN10
IN12
IN14
OUT0
OUT2
OUT4
OUT6
OUT8
OUT10
OUT12
OUT14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srm1Srm1-c01-v2Srm1-c02-v2

Table of Contents