Wiring Configuration - Fire-Lite MS-9200UDLS User Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Product Description
26
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
ANN-80 Current Draw
ANN-S/PG Current Draw
Total Worst Case Current Draw
Using this value and referring to the Wiring Distance Table 1.1 on page 25, it can be
found that the available options are:
926 feet maximum using 22 Gauge wire
2,344 feet maximum using 18 Gauge wire
3,731 feet maximum using 16 Gauge wire
5,906 feet maximum using 14 Gauge wire

1.8.7.1.2 Wiring Configuration

Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS Device
Figure 1.3 FACP wiring to ANN-BUS Device
= 3 X 0.040 amps
= 1 X.0.040 amps
MS-9200UDLS
MS-9200UDLS PN 52750:E1
= 0.120 amps
= 0.040 amps
= 0.160 amps
ANN-BUS/ACS BUS