Programming
CENTRAL STATION
1=TEST TIME INT

2=ACCOUNT CODE

3=24HR TST TIME
Primary/Secondary Screen #1
136

Test Time Interval

Pressing 1 while viewing Primary/Secondary Screen #1 will cause the following screens to be
displayed:
TEST TIME INTERVAL
1=24 HOURS
2=12 HOURS
3=8 HOURS
Test Time Interval Screen #1
1=6 HOURS
The test report sent to the Central Station phone number may be sent once every 6, 8, 12 or 24
hours. Select the desired Test Time Interval by pressing the corresponding digit in the screens
shown above.
Account Code
Pressing 2 while viewing Primary/Secondary Screen #1 will cause the following screen to be
displayed:
ACCOUNT CODE
4 CHAR RANGE 0-F
The Account Code, which is assigned by a Central Station, depends on the communication
format being used. The Account Code screen will have a flashing cursor in the lower left
corner. Enter the supplied account code using 0 - 9 and A- F keys.