2.7 UL Power-limited Wiring Requirements
Figure 2.11 Typical UL Power-limited Wiring Requirements
AC Power
Grounding Stud
MS-9200UDLS PN 52750:E1
Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet. All power-limited circuit wiring must remain at least 0.25" (6.35 mm) away
from any nonpower-limited circuit wiring and nonpower-limited circuit wiring must
enter and exit the cabinet through different knockouts and/or conduits. A typical wiring
diagram for the MS-9200UDLS is shown below.
Power-limited Circuits (Class 2)
Nonpower-limited Circuits
Ground Strap
To Batteries
01/27/09
Power-limited Circuits (Class 2)
Nonpower-limited Circuits
Installation
Power-limited Circuits
(Class 2)
maintain minimum 0.25"
between power-limited
and nonpower-limited
circuits wiring
Nonpower-limited
Circuits