4.6 Supervisory Operation

MS-9200UDLS PN 52750:E1
Third line in display: Z000 indicates the zone programmed to this device which,
in this example, is general alarm Zone 000. Note that a single device can be
programmed to five different zones but only the first zone will be displayed.
Fourth line in display:
Time; the current time in this example is 10:00A which represents 10:00 AM
Date; the current month, day and year in this example is 01 for January, 08 for
the 8th day of the month and 01 for the year 2001
Device Address; 1M001 in this example 1 represents SLC Loop, M represents
a module and 001 represents device address 001
Supervisory operation is similar to alarm operation but with the following differences:
The piezo sounder pulses ½ second On and ½ second Off
The Supervisory LED flashes ½ second On and ½ second Off
The LCD displays the status label Active Supervisory along with the device
name, type, address, adjective/noun, associated zones and time/date
Communicate the supervisory condition to the Central Station
The supervisory relay is activated
The alarm relay is not activated
NACs will not activate
Silenced alarms are not resounded
Timers are not started
Store event in history buffer
Terminate upload or download communications
Supervisory condition must be Acknowledged before the FACP can be reset
A typical Supervisory event would be displayed as illustrated in the following:
ACTIVE
10:00A 010806 1M001
Note that, like alarms, supervisory signals latch (except when programmed for
supervisory autoresettable) and can be assigned to software zones. Supervisory events
do not cause resound as do other alarm conditions. Open circuits in supervisory wiring
are processed by the control panel the same way as other trouble conditions. Refer to
"Alarm Operation" on page 160, for a description of the information displayed on the
control panel LCD.