Pre-Installation Planning - Environment
Environment
Environmental Operating Limits
The environmental conditions required for operating the HC900 Hybrid Controller are listed Table 6.
Ambient Temperature
Relative Humidity
Vibration
Mechanical Shock
Electromagnetic Interference (EMI) and
Radio Frequency Interference (RFI)
Power
Power Consumption
Class 1, Division 2 Installations
General Installation
38
Table 6 - Operating Limits and Installation Guidelines
Condition
Frequency
Acceleration
Acceleration
Duration
Voltage
Frequency (Hz)
HC900 Hybrid Controller Installation and User Guide
Specifications
32°F to 131°F (0°C to 55°C) or (0°C to 60°C) with derating
10 % to 90 % RH at 40°C (104°F)
14 Hz to 250 Hz
1 g
1 g
30 ms
Meets the requirements of the EMC directive, 89/336/EEC.
Evaluated to EN61326:1997 + A1 for emissions and
immunity.
100 Vac to 240 Vac
47 to 63 Hz
Typical 110VA@ 115VAC, maximum 130VA @ 264VAC
CONTROLLER RACK MUST BE MOUNTED INSIDE A
SECURE ENCLOSURE
Install per NEC requirements for Open Type Equipment
Revision 5
9/03