Analog Output Modules

Feature
Number of outputs
Isolation
Output device
Load resistance
Accuracy
D/A Resolution
Output Current
Minimum current sensing
Calibration Data
Failsafe Outputs
Diagnostics
Output Verification
Revision 5
9/03
4 isolated outputs per module
500 Vdc Channel-Channel
600 Vdc from logic
MOSFET
0 to 750 ohms
0.1% of full scale at reference conditions
12 bits
0 to 21.8mA into 0 to 750 Ohms, range selectable
> 3.5 mA per output
Data is stored in non-volatile memory.
Redundant Factory Calibration, with automatic rejection of Bad version
Individual Channel Field Calibration
Timeout causes outputs to be forced to configured values.
Monitoring of Factory Calibration, Field Calibration, Configuration, and +24 Vdc
power supply.
Feedback to CPU that indicates output current flowing.