SPECIFICATIONS

Electrical

Table 3 Electrical Specification
Parameter
Rated input
20 - 30 VAC; Class 2 transformer
voltage
IP model: 8 VA; controller and
actuator load (nothing connected to
Nominal Power
IO and COM)
Consumption
MSTP model: 6 VA; controller and
actuator load (nothing connected to
IO and COM)
IP model: 30 VA; maximum load
including external loads, Sylk™,
communication, BLE, universal IO,
and 20 VDC output (excluding the
load on the solid state relays).
MSTP model: 22 VA; maximum load
including external loads, Sylk™,
communication, BLE, universal IO
output, and 20 VDC output
Full Load
(excluding the load on the solid state
Power
relays).
Consumption
If the solid state relays are used, user
needs to determine the full load
power consumption (or VA rating) as
per the below example.
Example for a transformer load (VA);
if there is an addition of parallel load
from two solid state relays with 24
VAC @ 1.5 A: Total transformer load
on a fully loaded controller will be 30
VA + 72 VA = 102 VA.
Frequency
50 to 60 Hz
Range
Auxiliary
20 VDC @ 75 mA
Output

Operational Environment

Table 4 Operational Environment
Parameter
Storage
-40 °F to 150 °F (-40 °C to 66 °C)
Temperature
Operation
32 °F to 122 °F (0 °C to 50 °C)
Humidity
5 % to 95 % RH, non-condensing
Protection
IP20, NEMA -1
Pollution
Level 2
SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS
Specification
Specification

Hardware

Table 5 Hardware Specification
Parameter
Crossover processor NXP I.MRT,
CPU
Cortex M7
Memory
16 MB QSPI Flash, 16 MB SDRAM
Capacity
Ethernet
Two each RJ-45 Ethernet ports.
(IP Model only)
Real Time
Clock
Transmission or reception of BACnet
Small LED
and Modbus communication signal
(green)
Controller status such as normal
operation, firmware download,
Large LED
broken sensor, e.g. green, yellow or
red

Integrated Actuator

Table 6 Integrated Actuator Specification
Parameter
Torque
44 in-lbs (5 Nm)
Run Time
Mounting
Shaft
Shaft Length
Position feedback via integrated potentiometer
• Periodic synchronization not required.
• Additional diagnostic, for example, the command to
change the actuator position does not provide a
corresponding sensor reading if the actuator is
stuck or the potentiometer is damaged.
5
Specification
• 24-hour backup after power
failure.
• In case of power failure, the
controller includes a super
capacitor to retain the time set
with the built-in real time clock
for 24 hours. After 24 hours, the
time will reset to the factory
default time until the user
performs a BACnet Time Sync.
Specification
• Floating 108 s at 50 Hz
• Floating 90 s at 60 Hz
• Round 5/16 – 5/8 in (8 - 16 mm)
• Square 1/4 – 1/2 in (6 -13 mm)
1 5/8 in (41 mm)
31-00475-01