DC Input Module

Feature
Inputs
Input Voltage Range
Peak Voltage
Isolation
ON voltage level
OFF voltage level
Input impedance
Input current
Minimum On current
Minimum Off current
Base Power Required
Response Time
Revision 5
9/03
16 (sinking)
10 Vdc to 32 Vdc
32 Vdc
2 groups of 8 inputs/group; dielectric strength between groups: 42.4 Vdc (30
Vac)
9.5 Vdc minimum
3.5 Vdc maximum
2.6k ohms nominal
2.3 mA @ 12 Vdc
6.9 mA @ 24Vdc nominal
3.5 mA
1.5 mA
230 mA maximum for 5 Vdc; (no 24 Vdc power)
OFF to ON: 4 ms maximum; 2 ms nominal
ON to OFF: 4 ms maximum; 2 ms nominal
HC900 Hybrid Controller Installation and User Guide
Specifications - DC Input Module
Description
165