Specifications - AC Output Module

AC Output Module

Feature
Outputs
Isolation
Operating Voltage
Output type
Peak Voltage
AC Frequency
Transient Over-voltage
Protection
ON-Voltage drop
Maximum Load Current
Maximum Leakage Current
Maximum In-rush Current
Minimum Load
Base Power Required
Response Time
Fuses
168
8
Per output; Jumper comb is available for connecting "L1" terminals
85 Vac to 240 Vac
Triac
250 Vac
47 to 63 Hz
MOV
< 1.5 Vac (> 0.1 A)
< 3.0 Vac (< 01. A)
2 A per point, 8 A max. per module, resistive load
4 mA (240 Vac, 60 Hz)
1.2 mA (100 Vac, 60 Hz)
0.9 mA (100 Vac, 50 Hz)
60 A for 10 ms
50 mA
218 mA @ 5V
Off to On: 2 ms + 1/2 cycle
On to Off: 2 ms + 1/2 cycle
Replaceable; Wickmann part #3741315041. 3.15 Amp time lag fuse with
UL/CSA approval for 250 VAC