Appendix B Installation of Remote Termination Panels (RTPs) - Digital Input/Digital Output/Analog Output
16 Point DC Digital Input
Step
4
Connect field wiring.
Note: SDC+ in the wiring figure below refers to power that is disconnected from these screw terminals when
switch SW1 is open (0).
DC Supply
16 Point AC Digital Input
Step
1
ATTENTION: RTP and cables are intended for permanent installation within their own enclosure.
Mount RTP cable assembly to HC900 Controller (Figure 60).
Remove appropriate key tabs from terminal block to allow mating with the module. See page 64.
Connect desired cable to 16 point AC DI module at controller. Choose from:
900RTC-H010
900RTC-H025
900RTC-H050
Install AC DI module label into module connector cover.
Connect shield drain wire to the grounding bars at the base of the HC900 rack. All field-wiring
shields must be grounded as described in the shield grounding section (page 60).
198
1
2
3
4
5
6
7
21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Remote Terminal High Voltage Cable assembly, 1.0 meters long
Remote Terminal High Voltage Cable assembly, 2.5 meters long
Remote Terminal High Voltage Cable assembly, 5.0 meters long
HC900 Hybrid Controller Installation and User Guide
Action
8
9 10 11 12 13 14 15 16 17 18 19 20
Action
Revision 5
9/03